EasyManua.ls Logo

Thytronic NV10B - Profile A - Residual Overvoltage Settings

Thytronic NV10B
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
APPENDIX
106
NV10B - Manual - 04 - 2022
U>> Trip LEDs U>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Definite time
59 Second threshold definite time
State OFF | ON
Pickup value Un 0.50 ... 1.50 step = 0.01
U>>def Operating time
Value s
0.03 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Residual overvoltage - 59N
Common configuration
Residual voltage measurement type for 59N - direct/cal-
culated
3VoType59N UE | UEC
59N Operation from 74VT external 74VText59N OFF | Block
UE> Element
Setpoints
UE> Enable UE> Enable OFF | ON
UE> Curve type UE>Curve INVERSE | DEFINITE
UE> Reset time delay
Value s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
UE> Logical block UE>BLK1 OFF | ON
UE> Breaker failure UE>BF OFF | ON
UE> Start relays UE>ST-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
UE> Trip relays UE>TR-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
UE> Start LEDs UE>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
UE> Trip LEDs UE>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Definite time
59N First threshold definite time
State OFF | ON
Pickup value UEn 0.01 ... 0.70 step = 0.01
UE>def Operating time
Value s
0.07 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Inverse time
59N First threshold inverse time
State OFF | ON
Pickup value UEn 0.01 ... 0.50 step = 0.01
UE>inv Operating time tUE>inv s
0.10 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
UE>> Element
Setpoints
UE>> Reset time delay
Value s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
UE>> Logical block UE>>BLK1 OFF | ON
UE>> Enable UE>>BF OFF | ON
UE> Disabling by UE>> start UE>disbyUE>> OFF | ON
UE>> Start relays UE>>ST-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
UE>> Trip relays UE>>TR-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
UE>> Start LEDs UE>>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
UE>> Trip LEDs UE>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Definite time
59N Second threshold definite time
State OFF | ON
Pickup value UEn 0.01 ... 0.70 step = 0.01

Table of Contents

Related product manuals