APPENDIX
111
NV10B - Manual - 04 - 2022
Value s
0.03 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Inverse time
59 First threshold inverse time
State OFF | ON
Pickup value Un 0.50 ... 1.50 step = 0.01
U>inv Operating time tU>inv s
0.10 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
U>> Element
Setpoints
U>> Logical block U>>BLK1 OFF | ON
U>> Breaker failure U>>BF OFF | ON
U> Disabling by U>> start U>disbyU>> OFF | ON
U>> Start relays U>>ST-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
U>> Trip relays U>>TR-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
U>> Start LEDs U>>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
U>> Trip LEDs U>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Definite time
59 Second threshold definite time
State OFF | ON
Pickup value Un 0.50 ... 1.50 step = 0.01
U>>def Operating time
Value s
0.03 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Residual overvoltage - 59N
Common configuration
Residual voltage measurement type for 59N - direct/cal-
culated
3VoType59N UE | UEC
59N Operation from 74VT external 74VText59N OFF | Block
UE> Element
Setpoints
UE> Enable UE> Enable OFF | ON
UE> Curve type UE>Curve INVERSE | DEFINITE
UE> Reset time delay
Value s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
UE> Logical block UE>BLK1 OFF | ON
UE> Breaker failure UE>BF OFF | ON
UE> Start relays UE>ST-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
UE> Trip relays UE>TR-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
UE> Start LEDs UE>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
UE> Trip LEDs UE>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Definite time
59N First threshold definite time
State OFF | ON
Pickup value UEn 0.01 ... 0.70 step = 0.01
UE>def Operating time
Value s
0.07 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Inverse time
59N First threshold inverse time
State OFF | ON
Pickup value UEn 0.01 ... 0.50 step = 0.01
UE>inv Operating time tUE>inv s
0.10 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
UE>> Element

Table of Contents