EasyManua.ls Logo

Thytronic SME2-IS - Issue; Mechanical Tests; Climatic Conditions; Safety Instructions

Thytronic SME2-IS
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
12
SME2-IS - Manual - 06 - 2021
TECHNICAL CHARACTERISTICS
Tests for immunity to fast electrical transients/pulse trains (5/50 ns)
All the circuits 4 kV
Reference standards EN 60255-22-5, IEC 60255-22-5
EN 61000-4-5 IEC 61000-4-5
High energy pulses
U
aux
common mode 2 kV
U
aux
differential mode 1 kV
Reference standards EN 60255-22-6, IEC 60255-22-6
EN 61000-4-6 IEC 61000-4-6
Conducted electromagnetic fields
0.15...80 MHz AM 80% 1kHz 10 V
Reference standards EN 60255-22-7, IEC 60255-22-7
EN 61000-4-16 IEC 61000-4-16
Mains frequency voltage
Direct current 100 V
50 Hz continuous 100 V
50 Hz 1 s 300 V
0.015...150 kHz 10 -1 -1 10 V
Reference standards EN 61000-4-8, IEC 61000-4-8
50 Hz magnetic field
50 Hz continuous 100 A/m
50 Hz 1 s 1 kA/m
Reference standards EN 61000-4-10, IEC 61000-4-10
Damped oscillatory wave magnetic field
Damped oscillatory wave 0.1 MHz 30 A/m
Damped oscillatory wave 1 MHz 30 A/m
Issue
Reference standard IEC 60255-26
EN 60255-25 IEC 60255-25
EN 61000-6-4 IEC 61000-6-4
EN 55011 CISPR 32
Electromagnetic emissions
Auxiliary power conducted emission 0.15...0.5 MHz 79 dB mV
Auxiliary power conducted emission 0.5...30 MHz 73 dB mV
Radiated emission 30...230 MHz 40 dB mV/m
Radiated emission 230...1000 MHz 47 dB mV/m
Mechanical tests
Reference standard EN 60255-21-1 EN 60255-21-2 RMEC01
Vibration, impact, shock and seismic resistance tests for measurement relays and protection
equipment
EN 60255-21-1 Vibration tests (sinusoidal) Class 1
EN 60255-21-2 Impact and shock tests Class 1
EN 60068-2-64 Wide band random vibration Class 1
Climatic conditions
Reference standard IEC 60068-x ENEL R CLI 01 CEI 50
Environmental tests
Ambient temperature -25...+70 °C
Storage temperature -40...+85 °C
Relative humidity 10...95 %
Atmospheric pressure 70...110 kPa
Safety instructions
Reference standard IEC 60255-27
Pollution degree 3
Reference voltage 250 V
Reference category III
Reference specifications
Directional fault detector and measuring relay RGDM ST Prescriptions and test methods
ENEL GSTP011 Ver. 01 (26/07/2019)
ENEL GSTP012 Ver. 01 (26/07/2019)
ENEL GSTP013 Ver. 01 (26/07/2019)
ENEL GSTP901 Ver. 01 (06/12/2018)
Smart Termination ENEL DJ5400 - ENEL GSCT0051