EasyManua.ls Logo

Thytronic SME2-IS - Page 46

Thytronic SME2-IS
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46
46
SME2-IS - Manual - 06 - 2021
FUNCTIONAL CHARACTERISTICS
The gure below shows a rapid reclosing followed by a fault which opens the breaker within the
neutralisation time followed by a slow reclosing run on the fault within the discrimination time td1;
the reclosing is considered unsuccessful and the respective report is issued.
Rapid reclosing + slow
reclosing and subsequent
memorized reclosings
The gure below shows a rapid reclosing followed by a fault which opens the breaker within the
neutralisation time, followed by a slow reclosing and a fault detected beyond t
d1
but within the neu-
tralisation time t
r
; when t
r
times out, the memorized reclosing is run.
If the line is MIXED, t
d1
=0; if the fault occurs immediately, the sequence proceeds with a non-deni-
tive trip and wait for the rst memorized reclosing.
If the line is CABLE, t
d1
=5 s; if the fault recurs within t
d1
, the sequence continues with a denitive trip
and signals unsuccessful reclosing.
MIXED line
If the line is MIXED, and the fault occurs within t
r
, the sequence opens the breaker and the following
memorized reclosing is run when t
r
expires. Every subsequent memorized reclosing starts timers t
r
and t
d2
. If a fault occurs within t
r
, but after t
d2
, the sequence opens the breaker and the next memo-
rized reclosing occurs when t
r
expires; if, on the other hand, the fault is detected within t
d2
, a deni-
tive trip occurs and an unsuccessful reclosing is reported.
CABLE line
If the line is CABLE and a fault occurs within t
r
, but after t
d1
, the sequence opens the breaker and the
next memorized reclosing occurs when t
r
expires; if, on the other hand, the fault is detected within
t
d1
, a denitive trip occurs and an unsuccessful reclosing is reported. The sequence is repeated for
the congured number of memorized reclosings, using t
d2
in place of t
d1
.
After a denitive trip, each intentional closing (local or remote) starts t
r
.
If no tripping condition occurs within t
r
, the automation must change to the state denominated FA, in
which further automatic reclosing are disabled, thus enabling manual troubleshooting of the non-au-
tomated branch lines.
In FA status, any new detection of a fault must generate a denitive trip issued in base time, accom-
panied by an unsuccessful closing signal FR.
The FA status concludes when timer t
fa
expires. From that time on, every new fault detected will be
part of a new reclosing cycle.
t
Neutralisation timer
Discrimination timer
td1
Failed reclosing
Rapid reclosing followed by fault and subsequent slow reclosing on fault
t
Neutralisation timer
Discrimination timer
td1 td2
Failed reclosing
Rapid reclosing followed by fault and subsequent slow and memorized reclosings

Table of Contents

Other manuals for Thytronic SME2-IS