SME2-IS - Manual - 06 - 2021
FUNCTIONAL CHARACTERISTICS
51/67
51A/67A
+ AP trip
command
0
Tr> Tatt
&
Blind
0
Tatt+Tadd
BLIND held
Selective block function - FSL tripping logic
Tripping delay
Tripping delay
≥
0
Tatt
FSL2
In FSL2 mode: BLIND WAIT FOR FIRST FAULT OCCURRENCE ONLY and conditions:
• If the fault condition has been sent to UP, from that moment onwards any subsequent faults will be
sent to UP, without intentional delay.
• The intentional delay, resulting from the wait for the BLIND signal, will be start again automatically
when voltage is measured to be stable for 3 minutes consecutively.