SME2-IS - Manual - 06 - 2021
CALIBRATION AND START-UP
pressing a button. If you do not wish to wait for the 3 minutes to time out, enter the password
menu and quit it without entering the password (use the keys Left and Right until the message
password not ok >> displays
Changing the password
You can only set a new password after you have entered the existing one (password ok >>);
press Down the change password menu displays. Press Right to enter it. This menu allows
you to set a new password.
• Hold down the button Enter; the START and TRIP LEDs will ash to indicate you are in settings mode
and a cursor will display under the selected parameter
• Set the new password with the keys Up or Down using the keys Left and Right to move from one
character to the next
• Press Enter; the cursor will disappear and the TRIP LED will go out, with the START led will con-
tinue ashing
• Hold Enter down for a few seconds until the following message displays: Confirm settings?
• Respond to the prompt ENTER: YES to conrm, or RESET: NO to abort the change.
What to do if you have
forgotten or lost the password
If you lose or forget the password, you must restore the device's Database.
Proceed as follows:
• Launch a level 1 session
• Send the command Set Default Calibration in the menu Commands \ Default Calibrations
The command Set Default Calibration sets the password to the default value = 0000.
The Set Default Calibration restores the factory settings. All previous changes to the settings will be
lost.
Enter the desired regulations and check that they are correct!
The device's serial number must be entered to prevent IP address conicts with other devices on
the Ethernet network