6
7. Setting Up
Walk Test (Test Mode)
Turn the power to the unit ON. The lamp will immediately illuminate
as the unit goes through its “warm-up” period. After approximately
45 seconds the lamp will extinguish. This indicates the unit is wired
correctly and the unit is in Test Mode.
Try to remain outside the detection area during the warm-up period.
The unit will now operate during daytime as well as at night, illuminating
the lamp for approx. 3 seconds each time. This allows testing to be
carried out to establish whether the sensor is covering the required area.
Walk around the sensor to establish the detection area. The sensor
will detect within an approximate 8 metre diameter circle from the centre
of the sensor location with a 3m ceiling. As you cross a detection “zone”
the lamp will illuminate.
Now stand still until the lamp extinguishes (this should take approx.
3 seconds). Start moving again after 2 seconds. As you cross
each “zone” the lamp will illuminate.
Repeat the above, walking at various distances and angles to the unit.
This will help you to confirm the detection pattern.