Button “MENU”
5. Set the water volume to be treated:
Press the button DOWN. The screen will show the program 1, wich corresponds to the backwash interval,
that is, the number of regenerations in which the valve does not make a backwash. For up flow valves is not
necessary to perform a backwash in each regeneration. To adjust, press “Menu/confirm” and change the
value with UP and DOWN until the desired value. Press “Menu/confirm” to confirm.
6. Volume-to-treat settings:
Configuration for volume of water to be treated in m
3
, (options A-01, A-02, section 3). We will mark the
volume that can be decalcified, according to table 1.
Press the DOWN key. The display will show the amount of water in m3 that will pass through the resin after
the regeneration process. Press the "menu / confirmation" key again and the value will start blinking. You
can change this amount using the UP and DOWN buttons. Press "menu / confirmation" to confirm and move
to decimal setting. Modify the quantity with the "UP" / "DOWN" buttons.
Press "menu / confirmation" again to confirm the setting. Set the appropriate amount according to the amount
(liters) of resin and the hardness of the water. Refer to the corresponding value in Table 1.
Button “UP”
Button “DOWN”
Button “MENU”
Button “MENU”