74
3.2 BRAKING UNIT AND BRAKING RESISTOR UNIT
For Models L150 and L200 (220V Class 11, 15 kW)
R
3-Phase
L1(R)
S
Power Supply
L2(S)
200 to 240V
TL3(T)
MCCB
DC Reactor
(Option)
Motor
IM
Ground (100Ω or less)
1 2
U(T1)
V(T2)
W(T3)
AM
AC
(G)
MA
MB
MC
M1
M2
Analog
Monitor
FM
-
+
Multi-function Analog Output 0
to +10V 2mA
(Output Frequency at Factory
Setting)
Multi-function Contact Output
250 VAC 1A or less
30 VDC 1A or less
(Fault Output Signal at Factory Setting)
Multi-function Contact Output
250 VAC 1A or less
30 VDC 1A or less
(Signal during Running at Factory Setting)
TG 250
TG 300
Use sequencer break
power supply side on
overload relay trip
contact.
50/60 Hz
MC
Forward Run when
CLOSED
Multi-function
Contact input
Sequence Commom
Terminal (0V)
Shield Sheath
Connection Terminal
Freq. Setting Power
Supply +15V 20mA
Master Freq. Ref. 0
to 10V (20kΩ)
Master Freq. Ref.
4 to 20mA (250Ω)
[0 to 10V(20kΩ)input available]
Forward Run/Stop
Reverse Run/Stop
External Fault
Fault Reset
Multi-step Speed Setting 1
Multi-step Speed Setting 2
Factory
Setting
S1
S2
SC
S3
S4
S6
S5
G
FS
FV
FI
FC
0V
P
P
0V
4 to 20mA
0 to +10V
2kΩ
Master
Frequency
Reference
SA
MC
SA
TRX
TRX
Fault
Contact
20
18
MC
Overload Realay Trip Contact of
Breaking Resistor Unit
MC
12
SA
THRX
ON
OFFTHRX
M4
M3
OPEN COLLECTOR OUTPUT
(ZERO SPEED SIGNAL)
(OPTION)
3
Level
Delection
Braking Unit
(Option)
3
4
N
B
P
P0
P
B
1
2
Overload Relay Trip Contact
Braking Resistor
Unit(Option)
OPEN COLLECTOR OUTPUT

Related product manuals