EN-21T100 R
10. Door connection box
Fig.
The door connection box allows for the connection of a
safety edge, a wicket door contact and slack rope switches. The
wicket door contact and the slack rope switches are electrically
connected in series and are monitored by the control. If a wicket
door is available, the wicket door contact (Entrysense 6k8 model)
is connected to the door connection box. For this purpose, re-
move the 2kOhm resistor from the door connection box, to which
the Entrysense is clamped, and connect it there. The Entrysense
is tested in compliance with PLc as per EN13849-1 and is mon-
itored by the door control.
As slack rope switches, switches with forced actuation complying
with the specifications of EN60947-5-1, AnnexK are to be used.
The supply line of the door connection box is to be laid at the
door leaf, well protected against damage. With pulsed operation,
connect a closing edge safety device and select the correspond-
ing setting in menu item 35. Pressing the Prog button in
menu item35 for a longer time displays the measured resistance
value of the 8k2 closing edge. Example: Value 82 means 8k2.
Pressing the Prog button briefly will interrupt the display.
CAUTION
Crush hazard and risk of being struck by the
closing door
The pressure wave switches may only be actu-
ated after having been tested.
• For this purpose, select the value2 in menu
item35.
Fig.
Connect a door connection box with a break-away sensor
and an OSE (optical closing edge safety device).
Fig.
Connect a door connection box with a break-away sensor
and an 8k2closing edge safety device).
When using a RadioSafe module, a light grid or another
safety solution, connect the 8k2 resistor directly to terminal J3.
Value1 has to be selected in menu item35.
11. Light grid
Instead of the closing edge safety device, the following light grids
can be connected:
Fig.
A light grid by Telco with "SG14" testing. Set the value
to1 in menu item36.
Fig.
A light grid by Telco with "SG15" OSE interface. Set the
value to0 in menu item35.
Fig.
A light grid by CEDES with "GridScan/Mini-SB-2"OSE in-
terface. Set the value to0 in menu item35.
Fig.
A light grid by WITT with "LIGI" OSE interface. Set the
value to0 in menu item35.
12. Photoelectric sensor
Connect the photoelectric sensor as specified for the following
variants:
Fig.
2-wire photoelectric sensor LS2
Fig.
4-wire photoelectric sensor LS5 with testing
Fig.
Reflection light barrier
Then select the corresponding photoelectric sensor under menu
item36.
If you have selected "Photoelectric sensor mounted in the frame",
the next CLOSE run executed by the control is a "learning cycle"
for detecting the position.
NOTICE
Do not interrupt the learning cycle
The learning cycle must not be interrupted, so
that no incorrect position is recorded.
13. Anti crash sensor
Via a connected anti-crash sensor, inputJ6 detects when the cur-
tain is off guide and starts automatic threading up.
Fig.
One-way light barrier with relay output (SMR32xx /
SMT30xxC)
Fig.
One-way light barrier with transistor output (ELS-300 NO)
14. STOP circuit
Fig.
Emergency stop connection
Connect the emergency stop button to terminalJ4.3/4.
Fig.
Connection of the roll-up protection mechanism
To provide for protection from being drawn in, with fixed cable
routing a roll-up protection mechanism with an evaluation unit can
be connected to the safety circuitJ4.3/4. The evaluation unit must
comply with PLc Cat3 as per EN13849-1.
Also use this input to connect a spring break switch.
15. Key switch
When connecting a key switch to the connection terminal J7
(Fig.
), the control has to be programmed accordingly. Select
the desired function in menu item50 "Key switch function".
16. Radio receiver
For the use of a hand-held transmitter, attach the receiver module
(option) to J11 (Fig.
) and connect the antenna to J12. In order
to program the hand-held transmitters, follow the instructions
provided in Programming a radio hand-held transmitter in the
Programming chapter.
17. Relay outputs
The control provides two potential-free change-over contacts
(250VAC / 2A, 24V DC / 1A).
The 24V output at terminal X8 may be loaded with a maximum of
700mA.
Select the desired relay function in menu items45 and46.
Fig.
Connection of a red-green signaller. Select the value0 in
menu item45and the value1 in menu item46.
Fig.
Example: pre-warning time/ acoustic signal
Fig.
Connection for the mutual locking of 2doors (lock circuit).
Select the value2 or 3 in menu item50and the value0 in menu
item45.
Fig.
Connection for the mutual locking of 3doors (lock circuit).
Select the value2 or 3 in menu item50and the value0 in menu
items45 and 46.