B-131600XPi Series UPS Installation and Operation Manual – 60616-014
Item Brief Description
Description
On LCD
U A D
Svc/
QC
F Default Remark
439 Input Current Reference Oset
Adjustment
Ii Ref Oset - - - R/W R/W 0 Range: -96 to 96
440 DC undervoltage detection
delay
DCUV SW
DeDelay
- - - R/W R/W 2 Range: 1-32
441 DC overvoltage detection
delay
DCOV SW
DeDelay
- - - R/W R/W 2 Range: 1-32
442 DCUB Detection Delay DCUB SW
DeDelay
- - - R/W R/W 2 Range: 1-32
501 Battery Voltage Battery Voltage R R R R R 0 Units: Vdc
503 Battery Discharge Current Discharge Current R R R R R 0 valid only when discharging and zero for charged
mode
Units: 0.1 Adc
504 Battery Capacity Battery Capacity R R/W R/W R/W R/W 0 Range: 0 – 150
Units: %
505 Battery Runtime Battery Runtime R R R R R 400
506 Battery Charger Status Charger Status R R R R R 0 0 = Normal Charging
1 = Preventive Charging
2 = Stop Charging
507 Number of Battery Discharges Total Discharges R R/W R/W R/W R/W 0 Increment when backup mode more than 10 Sec
long
508 Calculated Battery Shutdown
Voltage
Cal Battery Vsd R R R R R Calculated from manufacturer’s data sheet.
Units: Vdc
509 Battery Life Remaining Batt Life Remain R R/W R/W R/W R/W 43800 Range: 0 – 43800
Units: Hr
511 Internal Battery Rated
Capacity in Ampere-Hour
Rated Ahr R R/W R/W R/W R/W 9 Battery capacity Ampere-Hour such as 7 AHr or 9
Ahr.
Range: 1 – 15
Units: Ahr
512 Number Internal Battery Packs
In Series String
No Batt(Series) R R/W R/W R/W R/W 18 Range: 0 – 48
513 Number Internal Battery
Strings in Parallel
No Batt(Paral) R R/W R/W R/W R/W 1 Number of internal battery strings. 3.6-14kVA=1,
18/22kVA=2.
Range: 1 – 24
514 Battery Installation Date Batt Ins Date R R/W R/W R/W R/W “20080101” YYYYMMDD
516 Battery Voltage Shutdown
Level
Batt SDown Level R R R/W R/W R/W 79 Percentage of nominal battery voltage.
Range: 0 – 120 Units: %