B-14 1600XPi Series UPS Installation and Operation Manual – 60616-014
Item Brief Description
Description
On LCD
U A D
Svc/
QC
F Default Remark
522
1
Enable External Battery
Cabinet 1
Enable BC1 R R/W R/W R/W R/W 0 0: Disable
1: Enable
523
1
Enable External Battery
Cabinet 1
Enable BC2 R R/W R/W R/W R/W 0 0: Disable
1: Enable
524 External Batt Cabinet
Installation Status
SbatEx - - - R/W R/W 0 0: Uninvested
1: Installed
525 External Batt Cabinet Number
of Battery Packs in Series
No Ex Bat(Series) R R/W R/W R/W R/W 0 Number of external batteries in series string. (24 for
one or two battery cabinets)
Range: 0 – 48
526 External Batt. Cabinet Number
of Battery Strings in Parallel
No Ex Bat(Paral) R R/W R/W R/W R/W 0 Number of external battery strings in parallel
Depends on UPS rating and Battery Cabinet Type.
Typically One external battery cabinet =3, two
cabinet =6
Range: 0 – 24
527 External Battery Cabinet
Rated Battery Capacity in
Ampere-Hour
Ex Batt Rated Ahr R R/W R/W R/W R/W 0 External matching battery cabinets use same battery
as internal: 9 Ah. (same as 511. Non-matching may
be di󰀨erent)
Range: 0 – 12
Units: Ahr
528 External Battery Cabinet
Rated Battery Discharge C
Rate
Ex Batt C Rate R R/W R/W R/W R/W 0 Range: 0 – 12
(Informational only. Not used in calculations.)
Units: C
529 External Battery Cabinet
Installation Date
Ext Batt Ins Date R R/W R/W R/W R/W “20080101” Format: YYYYMMDD
(Informational only. Not used in calculations.)
532 Battery Voltage Gain Vbat Gain - - - R/W R/W 8298 Used this value to convert AD value to actual unit.
Range: 1 – 32767
533 Battery Voltage O󰀨set Vbat O󰀨set - - - R/W R/W 0 Feedback O󰀨set adjustment due to hardware
components and software AD converter’s o󰀨set.
Range: -32768 – 32767
534 Battery Voltage AD Amount Vbat AD - - - R R 0 AD summation of 16 samples per half cycle.
544 Charger Reference (Normal
Charging Mode)
Charger
Ref(Norm)
- - - R/W R/W 55 Range: 0 – 320
545 Low Batery Level Low Batt Level R R R/W R/W R/W 90 % of battery nominal voltage.
Range: 0 – 100
Units: %
546 Charger Overvoltage
Detection Delay
VChrgOV DeDelay R R R/W R/W R/W 60 (Restart Required)
Range: 0 – 360
Units: Sec