547 Calculated Low Battery Level
in Vdc
Cal LB Level R R R R R 0 Calculated from level setup Command 545.
Units: Vdc
548 Charger Reference
(Preventive Charging Mode)
Charger Ref(Prev) - - - R/W R/W 150 Range: 0 – 320
549 Present Charger Reference Charger Ref - - - R R 0 Presently plotting charger reference
550 Charger Overvoltage
Detection Level
CHRGOV DeLevel - - - R/W R/W 117 Range: 100 – 150
Units: %
551 Charger Overvoltage warning
detection delay
CHRGOV
WrnDeDelay
- - - R/W R/W 8 Range: 1 – 240
Units: 1/2 Cyc
552 Charger Overvoltage warning
recovery delay
CHRGOV
WrnReDelay
- - - R/W R/W 1 Range: 0 – 59
Units: Sec
553 Charger Overvoltage fault
detection delay
CHRGOV
FltDeDelay
- - - R/W R/W 1 Range: 1 – 120
Units: Min
554 Enable Charger controller En ChrgCtler - - - R/W R/W 1 0: Disable
1: Enable
555 Restart Charger controller Restart ChrgCtler - - - R/W R/W 0 0: Disable
1: Enable
556 Batttery Current Multiplier Ibatt Multiplier - - - R/W R/W 12 Range: 1 – 255
557 Oset amp hour at 1 C
discharge rate
Oset AH Cap 1 - - - R/W R/W 22 Range: 0 – 255
558 Oset amp hour at 2 C
discharge rate
Oset AH Cap 2 - - - R/W R/W 29 Range: 0 – 255
559 Oset amp hour at 3 C
discharge rate
Oset AH Cap 3 - - - R/W R/W 36 Range: 0 – 255
560 Oset amp hour at 4 C
discharge rate
Oset AH Cap 4 - - - R/W R/W 39 Range: 0 – 255
561 Battery Voltage at 1 C
Discharge Rate
BattV at C Rate 1 - - - R/W R/W 120 Range: 1 – 255
562 Battery Voltage at 2 C
Discharge Rate
BattV at C Rate 2 - - - R/W R/W 118 Range: 1 – 255
563 Battery Voltage at 3 C
Discharge Rate
BattV at C Rate 3 - - - R/W R/W 114 Range: 1 – 255
564 Battery Voltage at 4 C
Discharge Rate
BattV at C Rate 4 - - - R/W R/W 113 Range: 1 – 255
565 True Discharge Battery
Capacity
True Discharge C - - - R/W R/W 7500 Range: 1 – 36000
Units: mAh