B-18 1600XPi Series UPS Installation and Operation Manual – 60616-014
Item Brief Description
Description
On LCD
U A D
Svc/
QC
F Default Remark
571-8 Over Charge Current Level Over Ch I Lvl - - R R/W R/W Set Charger overcurrent limit. This should be 0.8
Amp above allowed current at full discharge mode.
(Prameter 571-10)
To Set 3.8 Amp, enter 380.
This parameter aect both battery cabinet.
Range: 0 – 5000
571-9 Constant Voltage Detection
Level
CV Detect Lv - - R R/W R/W Set 3270 for 327 V oat votlage
Range: 0 – 4000
571-10 Constant Current Detection
Level
CC Detect Lvl - - R R/W R/W Set 300 for 3.00 Amp current limit
Range: 0 – 4000
571-11 Number of Current Sense No Of I Sense R R R R/W R/W Set 2, if two strings are parallel in battery cabinet.
Set 3, if three strings are parallel in battery cabinet.
Range: 0 – 4
571-12 Clear External Battery Cabinet
Fault
Clr Ext BC Fault - - R R/W R/W Range: 0 – 5
572-2 Battery Cabinet 1 Input
Voltage Calibration Factor
BC1 IP V GCali - - R R/W R/W Ask Factory for Calibration Procedure.
Range: 0 – 5000
572-3 Battery Cabinet 1 Output
Voltage Calibration Factor
BC1 OP V GCali - - R R/W R/W Range: 0 – 5000
572-4 Battery Cabinet 1 Total Charge
Current Calibration Factor
BC1 Tot I GCali - - R R/W R/W Range: 0 – 1000
572-5 Battery Cabinet 1 Input
Voltage oset Calibration
BC1 IP V Ocali - - R R/W R/W Range: -1000 – 1000
572-6 Battery Cabinet 1 Output
Voltage oset Calibration
BC1 OP V Ocali - - R R/W R/W Range: -1000 – 1000
572-7 Battery Cabinet 1 Current
oset Calibration
BC1 Tot I Ocali - - R R/W R/W Range: -1000 – 1000
572-8 Clear Battery Cabinet 1
Disconnect Warning
Clr BC1 DNC Wrn R/W R/W R/W R/W R/W Clear this parameter to clear battery diconnect warn-
ing for battery cabinet 1
Range: 750 – 1024
572-9 Constant Current Mode
Charger Reference BC1
CC Mode Chg Ref - - R R/W R/W This parameter set oat voltage. To increase oat
voltage, decrease reference.
This parameter aect only battery cabinet 1.
588 = ~ 327 V
Range: 540 – 1024