B-191600XPi Series UPS Installation and Operation Manual – 60616-014
Item Brief Description
Description
On LCD
U A D
Svc/
QC
F Default Remark
572-10 Constant Voltage Mode
Charger Reference BC1
CV Mode Chg Ref - - R R/W R/W This parameter set current limit. To increase current
limit, decrease reference.
This parameter aect only battery cabinet 1.
850 = ~ 3 Amp
Range: 540 – 1024
572-11 Battery Cabinet 2 Input
Voltage Calibration Factor
BC2 IP V GCali - - R R/W R/W Range: 0 – 5000
572-12 Battery Cabinet 2 Output
Voltage Calibration Factor
BC2 OP V GCali - - R R/W R/W Range: 0 – 5000
572-13 Battery Cabinet 2 Total Charge
Current Calibration Factor
BC2 Tot I GCali - - R R/W R/W Range: 0 – 1000
572-14 Battery Cabinet 2 Input
Voltage oset Calibration
BC2 IP V Ocali - - R R/W R/W Range: -1000 – 1000
572-15 Battery Cabinet 2 Output
Voltage oset Calibration
BC2 OP V Ocali - - R R/W R/W Range: -1000 – 1000
572-16 Battery Cabinet 2 Current
oset Calibration
BC2 Tot I Ocali - - R R/W R/W Range: -1000 – 1000
572-17 Clear Battery Cabinet 2
Disconnect Warning
Clr BC2 DNC Wrn R/W R/W R/W R/W R/W Clear this parameter to clear battery diconnect warn-
ing for battery cabinet 2
752-18 Constant Current Mode
Charger Reference BC2
CC Mode Chg Ref - - R R/W R/W This parameter set oat voltage. To increase oat
voltage, decrease reference.
This parameter aect only battery cabinet 2.
588 = ~ 327 V
Range: 750 – 1024
572-19 Constant Voltage Mode
Charger Reference BC2
CV Mode Chg Ref - - R R/W R/W This parameter set current limit. To increase current
limit, decrease reference.
This parameter aect only battery cabinet 2.
850 = ~ 3 Amp
Range: 540 – 1024
601 System Temperature
Control PCB’s I2C Device
System(CTL)
Temp
R R R R R 0 Thermostat on control PCB.
Units: °C
602 Battery Temperature Battery Temp R R R R R 0 Thermistor attached to the case of battery tray.
Units: °C