B-20 1600XPi Series UPS Installation and Operation Manual – 60616-014
Item Brief Description
Description
On LCD
U A D
Svc/
QC
F Default Remark
608 Current State of UPS Current State R R R R R 0: Shutdown [show Shutdown]
1: Initial Charge [show Shutdown]
2: Boostup [show Shutdown]
3: Normal (Online) [show Online]
4: Backup [show Backup]
5: Batttery Test [show Battery Test]
6: Bypass Normal [show Bypass]
7: Bypass Init [show Bypass]
8: Bypass Shutdown [show Bypass]
9: Startup [show Startup]
609 Operation Mode Transition
State Requested
Requested State R/W R/W R/W R/W R/W 1: Shutdown Request
2: Bypass Request
3: Online Request
4: Battery Test Request
610 Operation Mode Transition
Timer
Timed Operation R/W R/W R/W R/W R/W 0 Sec The timer upon whose expiration a mode transition
will be attempted by the system.
Range: 0 – 800
Units: Sec
611 EPO Contact State EPO Status R R R R R Report of EPO input contact status.
0: Open
1: Closed
612 UPS Faults Faults R/W R/W R/W R/W R/W Only accept zero to clear Fault bit map
613 UPS Warnings Warnings R R R R/W R/W Only accept zero to clear Warning bit map
614 UPS System Status UPS
Status(Comm)
R R R R R LSW is attached at every data package. See
the details of bit map UX3FN19 (Toshiba
Communication Protocol (TUCP 2.0) for external
Reference.doc
615 Run / Stop mechanical switch
state
RunStop SW
Status
R R R R R 0: Stop
1: Run
617 Service Port Communication
Status
SPort Status R R R R R 0 0: Unknown
1: Normal & OK
2: Idle – O (Disable)
3: Error
618 Internal Communication StatusInter Comm Status R R R R R 0 0: Unknown
1: Normal & OK
2: Idle or O (Disable)
3: Error