B-211600XPi Series UPS Installation and Operation Manual – 60616-014
Item Brief Description
Description
On LCD
U A D
Svc/
QC
F Default Remark
619 Security Level Control
(Enter Password)
Security Level R/W R/W R/W R/W R/W Reading will give the current security level
USER for User Level
ADMIN for Administration Level
DIST for Distrubutor Level
QCNSRV for Qc and Service Level
ENG for Engineering Level
NOTE: Three communication chanels have their
own security level variables
620 Manage Admin Password Manage Admin
PW
- R/W R/W R/W R/W ADMIN Change Admin Password
621 Reset Admin Password Reset Admin PW R/W R/W R/W R/W R/W 0 0 = do nothing
1 = reset administration password
623 Bypass Enable* En Bypass* - - - R/W R/W 1: Enabled DIP Switch, EEPROM’s Enable CVCF, and this
value will decide the system’s bypass availability
(Restart Required)
0: Disable
1: Enable
624 Enable Transfer to Bypass
while in Async mode
En Asyn Byp - - - R/W R/W 1: Enable When Disabled, the UPS will not prevent transfers to
bypass mode during periods when the frequencies
are out of synch.
0: Disable
1: Enable
625 Enable CVCF* En CVCF* - - - R/W R/W Constant Voltage, Constant Frequency Mode
(Restart Required)
0: Disable
1: Enable
626 CVCF Output Frequency* CVCF Frequency* - - - R/W R/W 6000 500 or 600 Only. Other values will default to 500
Systems.
(Restart Required)
Units: 0.1 Hz
634 System Date UPS Date R/W R/W R/W R/W R/W Depends on which protocol is used.
SNMP serial link and CAN communication –
1st Byte -> Day of Week (1 = Sunday, 2 = Monday,
…, 7 = Saturday)
2nd Byte -> Date
3rd Byte -> Month
4th Byte -> Year (without 2000)
Hyper terminal -> “DOW MM/DD/YYYY”