B-22 1600XPi Series UPS Installation and Operation Manual – 60616-014
Item Brief Description
Description
On LCD
U A D
Svc/
QC
F Default Remark
635 System Time UPS Time R/W R/W R/W R/W R/W Depends on which protocol is used.
SNMP serial link and CAN communication –
1st Byte -> Hour
2nd Byte -> Minute
3rd Byte -> Second
see the related document.
Hyper terminal -> “HH:MM:SS”
636 System Timestamp Timestamp R R R R R Current system timestamp (32 bits format)
637 Enable Inverter / Bypass
command from REYE
En Reye UPS Ctl R R/W R/W R/W R/W 1: Enabled RemotEye is allowed to switch UPS Inverter to/From
Bypass or not!
0: Diable
1: Enable
639 Enable Startup Delay* En Startup Delay* R R/W R/W R/W R/W 0: Disabled Delay Timer enable or disable during Normal startup
(Not Shutdown by battery or Not LAN Shutdown),
(Restart Required)
0: Disable
1: Enable
640 Startup Mode (Bypass or
Inverter)*
Startup Mode* R R/W R/W R/W R/W 0: Bypass The Operation Mode into which the UPS will
transition at expiration of the Start Up Delay timer
(when enabled). (Restart Required)
0: Bypass
1: Online
Any other value besides 0 and 1 will be considered
Shutdown
641 Startup Delay Timer Value* Startup Delay* R R/W R/W R/W R/W 0 (Restart Required)
Range: 0 – 800
Units: Sec
644 Remote ‘Shutdown’ Contact
State
Remote SD Status R R R R R 0 0: Open (deactivated)
1: Closed (activated)
645 Remote ‘Shutdown’ Contact
Mode Selection
Mode of Rmt
SDown
R R/W R/W R/W R/W 0: Bypass 0: Bypass state
1: Shutdown state while contact is closed. Return to
previous state when contact is open.
646 Enable LAN Shutdown En DCntct LANSD R R/W R/W R/W R/W 1: Enable
647 LAN Shutdown Signal
Permitted Time Window
DCntct LANSD
Wndw
R R/W R/W R/W R/W 600 Range: 0 – 800 Units: Sec
648 Remote ‘On Batteries’ Delay
Timer
BK DContact
Delay
R R/W R/W R/W R/W 10 Delay timer between actual event occurrence and
dry contact closure to signal external devices of the
event.
Range: 0 – 800
Units: Sec