B-231600XPi Series UPS Installation and Operation Manual – 60616-014
Item Brief Description
Description
On LCD
U A D
Svc/
QC
F Default Remark
649 Remote ‘Low Battery’ Delay
Timer
LB DContact Delay R R/W R/W R/W R/W 0 Delay timer between actual event occurrence and
dry contact closure to signal external devices of the
event.
Range: 0 – 800
Units: Sec
652 Enable Battery Test on UPS
Startup*
En Batt Test Sup* R R/W R/W R/W R/W 0: Disabled Forces a battery test when UPS starts after normal
shutdown.
(Restart Required)
0: Disable
1: Enable
653 Enable Battery Test* En Batt Test* R R/W R/W R/W R/W 1: Enabled (Restart Required)
0: Disable
1: Enable
654 Battery Test Condition Status Batt Test Cond. R R R R R 0 0 = Battery test prohibited because of battery test
interval setup
1 = Battery test OK to perform
655 Battery Test Frequency Batt Test Freq R R/W R/W R/W R/W 2: Monthly allow
0: only daily
1: only weekly
2: only monthly (Default for other values)
656 System Temperature
Compensation
Sys. Temp. Comp. - - - R/W R/w -5 Range: -20 – 20
Units: °C
657 Service Port Mode Service Port Mode - - - R/W R/W 1: Protocol Rqrd. 0: Terminal mode (no handshake, no error check)
1: Toshiba UPS Communication Protocol 2-0 mode
658 Enable Restart
(After Battery Shutdown)
En Restart R R/W R/W R/W R/W 1: Enable 0: Disable
1: Enable
659 Restart Delay
(After Battery Shutdown)
Restart Delay R R/W R/W R/W R/W 10 Sec Range: 0 – 800
Units: Sec
660 Enable Auto Transfer
(Current Limit)
En AutoXfer R R/W R/W R/W R/W 1: Enabled 0 = keep inverter,
1 = go to bypass and come back to inverter after
time delay CMD662
662 Auto ReTransfer Delay
(Current Limit)
AutoReXfer
Window
R R/W R/W R/W R/W 3 Sec Time period to wait after current limit occurrence
before attempting tranfer back Online.
Range: 0 – 600
Units: Sec
663 Service Port Baud Rate
Settings*
Srv Port Baud* R R/W R/W R/W R/W 3 no hardware control, no parity, 1 stop bit, 8 bits of
data and baud rate are (Restart Required)
0: 9600
1: 19200
2: 38400
3: 57600