B-28 1600XPi Series UPS Installation and Operation Manual – 60616-014
Item Brief Description
Description
On LCD
U A D
Svc/
QC
F Default Remark
831 LCD Test Mode En LCD Test - - - R/W R/W 0
832 Buzzer Test Mode En Buzz Test - - - R/W R/W 0
833 Backlight Test Mode En Blight Test - - - R/W R/W 0
839 Test Result Test Result R/W R/W R/W R/W R/W
840 Display Debug Info Disp DBG Info - - - R/W R/W 0 Range: 0 – 65535
850 RemotEye Installation Date RMTI Ins Dat R/
(W by
SNMP
Only)
R/
(W by
SNMP
Only)
R R R “20080101” YYYYMMDD
Note: Only SNMP can write. Others, read only.
851 RemotEye Version RMTI Ver R/
(W by
SNMP
Only)
R/
(W by
SNMP
Only)
R R R Note: Only SNMP can write. Others, read only.
852 RemotEye IP Address RMTI IP R/
(W by
SNMP
Only)
R/
(W by
SNMP
Only)
R R R Ex. “10.128.33.5” Cfg. Of RE parms can be done via
re comm.port
Note: Only SNMP can write. Others, read only.
853 RemotEye Network Mask
Address
RMTI Mask IP R/
(W by
SNMP
Only)
R/
(W by
SNMP
Only)
R R R Ex. “255.0.0.0”
Note: Only SNMP can write. Others, read only.
854 RemotEye Gateway Address RMTI Gway IP R/
(W by
SNMP
Only)
R/
(W by
SNMP
Only)
R R R Ex. “10.128.33.1”
Note: Only SNMP can write. Others, read only.
855 RemotEye Installation Status SRMTI R/
(W by
SNMP
Only)
R/
(W by
SNMP
Only)
R R R 0 Note: Only SNMP can write. Others, read only.
856 SNMP Port’s Baud Rate
Setting*
RMTI Baud * R R/W R/W R/W R/W 3 no hardware control, no parity, 1 stop bit, 8 bits of
data (Restart Required)
baud rate
0: 9600
1: 19200
2: 38400
3: 57600