A71600XPi Series UPS Installation and Operation Manual – 60616-014
Non–Standard Model: 5.2 kVA
Unit (Capacity) 5.2 kVA (4.4 kW)
1
General
Typeform H3BG2L052C61T
Certications UL 1778, CUL, RoHS Compliant
Input Characteristics
Input Voltage
1
Single-phase, 208/240 Vac, +10%
1,4
(to -30% at typical 70% load)
Input Frequency 45 – 65 Hz (auto-sensing)
Input Capacity 5.2 kVA
Input /(Max Input) Current @208V 28.6 (30.3) A
Input/(Max. Input) Current @240V 24.8 (26.2) A
Input Power Factor 0.98 Typical, 0.95 Minimum@ 100% Load
Current THD (linear load) < 5% total harmonic distortion
Internal AC Input Breaker Rating 50 A/277 V
Battery Characteristics
Battery Type Valve Regulated Lead Acid, Flame Retardant
Backup time, fully charged @ 0.7 power
factor, 77 °F
8 min.
2
Backup time, fully charged @ 0.85 power
factor, 77 °F
7 min.
2
Recharge Time 24 hr. (full), 12 hr. (90%) for internal batteries only
3
Battery Voltage (Nominal) 216 Vdc
Output Characteristics
Output Voltage Single-phase, 240/208/120 V
Output Voltage Regulation = ± 3%
Output Frequency ±0.5 Hz/1.0 Hz/1.5 Hz (factory or authorized service center selectable only)
AUTO/MAN Frequency Factory or authorized service center selectable only
Voltage THD < 3% for linear load; < 6% for non-linear load
Common-Mode Noise < 0.5 Vrms
Rated Load Power Factor
1
0.85 (0.6 – 1.0) lagging
E󰀩ciency (ac-dc-ac) ≥83%
Voltage Transient < ±8% (Load of 0 – 100 %)
Voltage Transient Recovery 50 ms to within 2% of nominal
Rated Output Current (rms) 21 A
1. Input/output gures rated for 240 volts unless otherwise stated. Output ratings given for 0.85PF are only valid when
the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
2. Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site.
3. An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation.
4. If Vin is below the minimum Vin window, the UPS goes to Battery Mode. If the UPS is in Fault and Vin is below the minimum
Vin window, the UPS goes to Bypass Mode