B-11600XPi Series UPS Installation and Operation Manual – 60616-014
Appendix B: 1600XPi Command Parameter Table
Access: U - User, A - Admin, D - Dealer, Svc/QC - Service /QC, F - Factory
R - Read only, R/W Read and Write
* - Changing parameter requires restarting Unit.
Item Brief Description
Description
On LCD
U A D
Svc/
QC
F Default Remark
001 UPS Manufacturer Manufacturer R R R/W R/W R/W “TOSHIBA”
002 UPS Typeform* Typeform* R R R R/W R/W “UH3B2B060C6” See Toshiba UPS Typeform document
At startup, rmware looks at kVA setting to calculate
rated input/output current and power factor. It will
default to 6 kVA rated value if kVA number is not pre-
dened values.
Also, Latched in UPS Overall Status Bit Map
(Restart Required)
003 UPS Serial Number Serial No R R R R/W R/W “080112345” YYMMSSSSS
YY – 2 digits of year
MM – 2 digits of month
SSSSS – 5 digits serial numbers
004 UPS Main Firmware Version Main FWare Ver R R R R R “UH3MSV01000” UXXYFVMMRRR
U – UPS
XX – 2 Alpha Numeric UPS Product Line (F3, H3)
Y – uC Projects (M – Main, S – Sub, D – Display)
FV – Firmware Version
MM – Major version
RRR – Minor version
005 UPS Main Boot Sector Version Main BSector Ver R R R R R “UH3MBS01000” UXXYBSMMRRR
U – UPS
XX – 2 Alpha Numeric UPS Product Line (F3, H3)
Y – uC Projects (M – Main, S – Sub, D – Display)
BS – Boot Sector
MM – Major version
RRR – Minor version
006 UPS Main Boot Loader
Version
Main BLoader Ver R R R R R “UH3MBL01000” UXXYBLMMRRR
U – UPS
XX – 2 Alpha Numeric UPS Product Line (F3, H3)
Y – uC Projects (M – Main, S – Sub, D – Display)
BL – Bootloader Version
MM – Major version
RRR – Minor version
Parameter Access 1600XP