B-51600XPi Series UPS Installation and Operation Manual – 60616-014
Item Brief Description
Description
On LCD
U A D
Svc/
QC
F Default Remark
128 Input Current Reference
Phase Adjustment*
Iref Phase Adj* - - - R/W R/W 14800 Time delay adjustment to sync the phase of input
voltage and current due to hardware and software
delay.
(Restart Required)
Range: 0 – 32767
Units: duS
129 Input Undervoltage Warning
Detection Delay
VIUV DeDelay - - - - R/W 1 Input Under Voltage Error detection delay in
consecutively.
Range: 0 – 600
Units: 1/2 Cyc
130 Input Undervoltage Warning
Recovery Delay
VIUV ReDelay - - - - R/W 8 Input Over Voltage Error recovery delay in
consecutively
Range: 0 – 600
Units: 1/2 Cyc
131 Input Overvoltage Warning
Detection Delay
VIOV DeDelay - - - - R/W 1 Input Under Voltage Error detection delay in
consecutively
Range: 0 – 600
Units: 1/2 Cyc
132 Input Overvoltage Warning
Recovery Delay
VIOV ReDelay - - - - R/W 8 Input Over Voltage Error recovery delay in
consecutively
Range: 0 – 600
Units: 1/2 Cyc
133 Input Frequency Warning
Detection Delay
FIERR DeDelay - - - - R/W 4 Input Frequency Error detection delay in
consecutively
Range: 0 – 300
Units: 1 Cyc
134 Input Frequency Warning
Recovery Delay
FIERR ReDelay - - - - R/W 8 Input Frequency Error recovery delay in
consecutively
Range: 0 – 300
Units: 1 Cyc
135 Input Voltage in percentage Input Voltage(%) R R R R R 0 Ratio of input voltage to rated input voltage.
Units: %
136 Input Current in percentage Input Current(%) R R R R R 0 Ratio of input current to rated input current.
Units: %
137 Calculated Input Undervoltage
Warning Detection Level
VIUV DeLevel R R R R R 0 UPS calculates input voltage detection level
according to output power (W) percentage, Gradient,
Section and Rated values.
Units: V
138 Calculated Input Undervoltage
Warning Recovery Level
VIUV ReLevel R R R R R 0 UPS Calculates input voltage recovery level
according to detection level and hysteresis.
Units: V