B-6 1600XPi Series UPS Installation and Operation Manual – 60616-014
Item Brief Description
Description
On LCD
U A D
Svc/
QC
F Default Remark
139 Rated Active Input Power (W) Rated InPower(W) R R R R R 0 UPS calculates at the startup according to typeform,
eciency and rated power factor.
Units: W
141 Input Frequency Setup in
Case of Input Frequency
Detection Error*
Freq on FIERR* R R/W R/W R/W R/W 6000 This frequency setup is used after UPS could not
determine input frequency in 3 Seconds. Then UPS
determine output frequency according to DIP Switch
or EEPROM setup.
Range: 500 – 600
Units: dHz
201 Output Power Supply
Conguration
Output Cong R R R R R 0 = unknown (>= 0, < 199)
1 = 200V – 60Hz (>= 200, <207)
2 = 200V – 50Hz (>= 200, <207)
3 = 208V – 60Hz (>= 208, < 229)
4 = 208V – 50Hz (>= 208, < 229)
5 = 230V – 60Hz (>= 230, < 239)
6 = 230V – 50Hz (>= 230, < 239)
7 = 240V – 60Hz (>= 240, < 32767)
8 = 240V – 50Hz ( >= 240, < 32767)
9 = 220V – 60Hz
10 = 220V – 50Hz
11 = 120V – 60Hz
12 = 120V – 50Hz
These numbers are stored in recording features.
Range: 0 – 15
202 Number of Output Lines No of Output Line R R R R/W R/W 1 Range: 1 – 2
203 Output Voltage
(Total)
Output Voltage R R R R R 0 Units: Vrms
204 Output Current
(Total)
Output Current R R R R R 0 Units: 0.1 Arms
205 Output Frequency
(Total)
Output Frequency R R R R R 0 Calculated only at Bypass mode and inverter mode.
Set to zero for other modes.
Units: 0.1 Hz
206 Output Active Power (W) Output Power(W) R R R R R 0 -1 if output active power can not be calculated
(Bypass Mode).
Units: W
207 Output Apparent Power (VA) Output Power(VA) R R R R R 0 Units: VA
209 Output Load Percentage
(Total)
Output Load (%) R R R R R 0 Dened as output current percentage or output
active power whichever higher.
Units: %