B-71600XPi Series UPS Installation and Operation Manual – 60616-014
Item Brief Description
Description
On LCD
U A D
Svc/
QC
F Default Remark
215 Rated Output Voltage
(Total)
Rated Vout R R/W R/W R/W R/W 240 Must be non-zero value. Undened behavior if
diveded by zero.
Range: 1 – 300
Units: Vrms
216 Rated Output Current
(Total)
Rated Iout R R R R/W R/W 250 Calculated from typeform and not writable.
Range: 0 – 1500
Units: 0.1 Arms
217 Rated Output Frequency
(Total)
Rated Fout R R R R R 0 Determined according to DIP switch or EEPROM
setup.
Units: 0.1 Hz
218 Rated Output Active Power Rated Pout(W) R R R R R 0 UPS calculates at the startup according to typeform,
e󰀩ciency and rated power factor.
Units: W
219 Rated Output Apparent Power Rated Pout(VA) R R R R R 0 UPS calculates at the startup according to typeform,
e󰀩ciency and rated power factor.
Units: VA
220 Output Under Voltage Fault
Detection Level
VOUV DeLevel R R R R/W R/W 90 Output Under Voltage Detection level in percentage
of Rated Output Voltage.
Range: 0 – 100
Units: %
222 Output Overvoltage Fault
Level
VOOV DeLevel R R R R/W R/W 110 Output Over Voltage Detection level in percentage
of Rated Output Voltage.
Range: 100 – 150
Units: %
224 Output Frequency
Synchronization Range
Fo Syn Window R R R R/W R/W 10 Output voltage will follow input voltage if the
di󰀨erence of input and output are within this value
(according to slew rate).
Range: 1 – 30
Units: 0.1 Hz
225 Output Frequency
Slew Rate
Fo Slew Rate - - - R/W R/W 10 The smallest control amount to add or subtract from
the current output frequency. Ups converts to a
correct value of per cycle instead of per second.
Range: 1 – 30
Units: 0.1 Hz
226 Output Voltage Adjustment
(Total)
Vout Adjust R R/W R/W R/W R/W 0 End user’s manual adjustment for output voltage
if desired. 1 increment or decrement will give
approximately 1 Vrms output.
Range: -10 – 10
227 Output Current 100% Amount Iout 100% Amount - - - R/W R/W 250 Range: 0 – 1500
Units: 0.1 A