B-8 1600XPi Series UPS Installation and Operation Manual – 60616-014
Item Brief Description
Description
On LCD
U A D
Svc/
QC
F Default Remark
228 Output Overload Warning/
Fault Detection Level in
Percentage
OOL Delevel - - - R/W R/W 110 Range: 0 – 150
Units: %
229 Output Overload Warning/
Fault Detection Delay at 125%
@ 25
0
C
OOL DeDelay - - - R/W R/W 30 Range: 0 – 300
Units: Sec
230 Output Overload Warning
Recovery Level in Percentage
OOL ReLevel - - - R/W R/W 105 Range: 90 – 120
Units: %
231 Output Overload Warning
Recovery Delay
OOL ReDelay - - - R/W R/W 160 Range: 120 – 1000
Units: Sec
232 Output Voltage
Compensation
Vout Comp. Step - - - R/W R/W 20 Output voltage will be compensated according to
this setup and current percentage.
Range: 1 – 200
Units: 1 Cyc
233 Output Voltage Gain
(Phase A or Total)
Vout Gain - - - R/W R/W 7987 Used this value to convert AD value to actual unit.
Range: 1 – 32767
234 Output Voltage O󰀨set
(Phase A or Total)
Vout O󰀨set - - - R/W R/W 0 Feedback O󰀨set adjustment due to hardware
components and software AD converter’s o󰀨set.
Range: -32767 – 32767
235 Output Voltage AD Amount
(Phase A or Total)
Vout AD - - - R R 0 AD summation of 16 samples per half cycle.
242 Output Current Gain
(Phase A or Total)
Iout Gain - - - R/W R/W 1131 Rated at 240 V output voltage.
Used this value to convert AD value to actual unit.
Range: 1 – 32767
243 Output Current O󰀨set
(Phase A or Total)
Iout O󰀨set - - - R/W R/W 0 Feedback O󰀨set adjustment due to hardware
components and software AD converter’s o󰀨set.
Range: -32767 – 32767
244 Output Current AD Amount
(Phase A or Total)
Iout AD - - - R R 0 AD summation of 16 samples per half cycle.
251 Output Voltage Reference
Phase Adjustment for 60 Hz*
Vref PhAdj 60 Hz* - - - R/W R/W -8 Time delay adjustment to sync the actual phase of
output and plotting. (Restart Required).
Range -64 – 64
252 Phase Lock Loop Controller’s
Propotional Gain
Pll Gp - - - - R/W 4 Range: 0 – 128
Units: /256
253 Phase Lock Loop Controller’s
Integral Gain
Pll Gi - - - - R/W 2 Range: 0 – 128
Units: /256