B-91600XPi Series UPS Installation and Operation Manual – 60616-014
Item Brief Description
Description
On LCD
U A D
Svc/
QC
F Default Remark
254 Output Voltage Reference
Amplitude
Vref Amplitute - - - R/W R/W 246 Calibrated at no Load output voltage.
Range: 0 – 300
Units: /128
255 Timer 3 Oset Remainder T3 Oset Remain - - - - R/W 350 Range: 0 – 1500
Units: /128
256 DC to AC Eciency DC-AC Eciency - - - R/W R/W 81 Range: 0 – 100
Units: %
257 Frequency Syn to Asyn
Warning Detection Delay
Freq Asyn
DeDelay
- - - - R/W 4 Range: 0 – 300
Units: 1 Cyc
258 Frequency Asyn to Syn
Recovery Delay
Freq Syn ReDelay - - - - R/W 8 Range: 0 – 300
Units: 1 Cyc
259 Phase Syn to Asyn Warning
Detection Delay
Ph. ASyn DeDelay - - - - R/W 4 Range: 0 – 300
Units: 1 Cyc
260 Phase Asyn to Syn Recovery
Delay
Ph. Syn ReDelay - - - - R/W 8 Range: 0 – 300
Units: 1 Cyc
261 Rated Power Factor Rated PFactor R R R R/W R/W 85 Calculated from typeform and rated voltage.
Range: 0 – 120
Units: 0.01
262 AC to AC Eciency AC-AC Eciency - - - R/W R/W 85 Range: 0 – 100
Units: %
264 OutputTo NoOutput or
NoOutput to Output mode
Gates transfer timing at Vout*
Gates Xfer Vout* - - - - R/W 75 Output to no output or no output to output mode
transfer timing in degree. Other mode, transfer
timing is at zero cross (Restart Required).
Range: 60 – 180
Units: 1 Cyc
265 Overload Detection Disable
Delay
OL Disable Delay - - - - R/W 8 Range: 0 – 16
Units: 1/2 cyc
266 Present plotting output voltage
reference amplitute
Present VoutRef - - - R R 0 uC generated reference amplitude.
267 Output Voltage Reference
Phase Adjustment for 50 Hz*
Vref PhAdj 50 Hz* - - - R/W R/W -7 Range: -64 – 64
268 Output Power Limited by
Converter (1) / Transformer (0)
Cnv/Xfmer Lmt - - - R/W R/W 0 power calculation is limited by
1 = input converter limited
0 = output transformer limited (default)
269 Output Voltage before
Tranformer Compensation
Vout B4 Comp. - - - R/W R/W 0 Units: V