B-10 1600XPi Series UPS Installation and Operation Manual – 60616-014
Item Brief Description
Description
On LCD
U A D
Svc/
QC
F Default Remark
270 Output Current before
Tranformer Compensation
Iout B4 Comp. - - - R/W R/W 0 Units: 0.1 A
271 Inverter Mode A CompensationComp. Ainv - - - R/W R/W 2 Range: 0 – 512
Units: /128
272 Inverter Mode B
Compensation
Comp. Binv - - - R/W R/W 10 Range: 0 – 512
Units: /128
273 Inverter Mode C
Compensation
Comp. Cinv - - - R/W R/W 0 Range: 0 – 512
Units: /128
274 Bypass Mode A Compensation Comp. Abyp - - - R/W R/W 3 Range: 0 – 512
Units: /128
275 Bypass Mode B CompensationComp. Bbyp - - - R/W R/W 7 Range: 0 – 512
Units: /128
276 Bypass Mode C
Compensation
Comp. Cbyp - - - R/W R/W 1 Range: 0 – 512
Units: /128
277 Overload Time Window OL Time Wndw - - - R/W R/W 10 Range: 0 – 30
Units: min
278 Rated Output Primary
Transformer
Rated OutXfmer(P) - - - R/W R/W 230 Range: 200 – 300
Units: V
279 50 Hz Derating 50Hz Derating - - - R/W R/W 100 Range: 50 – 150
Units: %
280 60 Hz Derating 60Hz Derating - - - R/W R/W 100 Range: 50 – 150
Units: %
301 Bypass Power Supply
Conguration
Bypass Cong R R R R R Always, the same as input conguration
0 = unknown (>= 0, < 199)
1 = 200V – 60Hz (>= 200, <207)
2 = 200V – 50Hz (>= 200, <207)
3 = 208V – 60Hz (>= 208, < 229)
4 = 208V – 50Hz (>= 208, < 229)
5 = 230V – 60Hz (>= 230, < 239)
6 = 230V – 50Hz (>= 230, < 239)
7 = 240V – 60Hz (>= 240, < 32767)
8 = 240V – 50Hz ( >= 240, < 32767)
9 = 220V – 60Hz
10 = 220V – 50Hz
11 = 120V – 60Hz
12 = 120V – 50Hz
These numbers are stored in recording features
302 Number of Bypass phases No Of Bypass Line R R R R/W R/W 1