B-111600XPi Series UPS Installation and Operation Manual – 60616-014
Item Brief Description
Description
On LCD
U A D
Svc/
QC
F Default Remark
303 Bypass Voltage
(Total)
Bypass Voltage R R R R R 0 Always the same as input voltage.
Units: Vrms
304 Bypass Current
(Total)
Bypass Current R R R R R 0 Only valid at bypass mode and zero for other ups
mode.
Units: 0.1 A
rms
305 Bypass Frequency
(Total)
Bypass Frequency R R R R R 0 Always the same as input frequency.
Units: 0.1 Hz
307 Bypass Apparent Power (VA) Bypass Power(VA) R R R R R 0 Only valid at bypass mode and zero for other ups
mode.
Units: VA
315 Bypass Undervoltage Warning
Detection Level
VBypUV DeLevel R R R R/W R/W 62 Range: 0 – 100
Units: %
316 Bypass Undervoltage Warning
Recovery Level
VBypUV ReLevel R R R R/W R/W 66 Range: 0 – 100
Units: %
317 Bypass Overvoltage Warning
Detection Level
VBypOV DeLevel R R R R/W R/W 284 Range: 0 – 500
Units: V
318 Bypass Overvoltage Warning
Recovery Level
VBypOV ReLevel R R R R/W R/W 274 Range: 0 – 500
Units: V
320 Bypass Overload Fault
Detection Delay at 125% @
25
0
C
BypOL DeDelay - - - R/W R/W 600 Range: 0 – 1000
Units: sec
339 Bypass Undervoltage
Detection Delay
VBypUV DeDelay - - - - R/W 1 Range: 0 – 600
Units: 1/2 cyc
340 Bypass Undervoltage
Recovery Delay
VBypUV ReDelay - - - - R/W 128 Range: 0 – 600
Units: 1/2 cyc
341 Bypass Overvoltage Detection
Delay
VBypOV DeDelay - - - - R/W 1 Range: 0 – 600
Units: 1/2 cyc
342 Bypass Overvoltage Recovery
Delay
VBypOV ReDelay - - - - R/W 128 Range: 0 – 600
Units: 1/2 cyc
343 Bypass Frequency Error
Detection Delay
FBypERR
DeDelay
- - - - R/W 4 Range: 0 – 300
Units: cyc
344 Bypass Undervoltage
Detection Delay
FBypERR
ReDelay
- - - - R/W 128 Range: 0 – 300
Units: cyc
401 DC Bus Voltage
(Total)
DC Bus Total R R R R R 0 Units: Vdc