3 SPECIFICATION
3.6.3 CH.
input range setting (Address RWwm+1H, RWwm+2H)
(1) Set the analog input range per channel.
(2) Operation is performed according to the setting made for the leading edges of the
initial data setting request flag (RY(n+1)9).
(3) The default is as follows.
AJ65VBTCU-68ADVN : -10 to +10V
AJ65VBTCU-68ADIN : 4 to 20mA
b15 b12 b11 b8 b7 b4 b3 b0to
CH.4
to
CH.3
to
CH.2
to
CH.1RWwm+1
b15 b12
b11 b8 b7 b4 b3 b0to
CH.8
to
CH.7
to
CH.6
to
CH.5RWwm+2
Input Range Set Value
-10 to +10V 0H
0 to 5V 1H
1 to 5V 2H
User range setting 1 (-10 to +10V) 3H
AJ65VBTCU-68ADVN
User range setting 2 (0 to 5V) 4
H
4to 20mA 0H
0 to 20mA 1H
AJ65VBTCU-68ADIN
User range setting (0 to 20mA) 2
H
POINT
If the set value is outside the setting range, error "20 " occurs, the "RUN" LED
flickers at intervals of 0.1s, and all channels do not make A/D conversion.
indicates the channel No. where the error occurred.