(2) AJ65VBTCU-68ADIN
1 Shield
2
FG1
Signal souce 0 to 20mA
AG
250
CH.8 I+
CH.8 I-
NC
SLD
CON8 CH.8
1
2
3
4
250
CH.1 I+
CH.1 I-
NC
SLD
CON1 CH.1
1
2
3
4
1 Shield
2
500k
500k
500k
500k
3
1 Use a two-core twisted shield line for the power cable.
2 Indicates the AJ65VBTCU-68ADIN input resistor.
3 Always perform grounding for FG1. When there is a lot of noise, it may be better ground AG
as well.
If the grounding wiring (grounding yes/no) is changed after the offset and gain are set,
perform the setting of the offset/gain values again.
POINT
A/D conversion values are fluctuated by self-heating within approx. 30 minutes
after power is turned ON.
Do not insert the one-touch connector plug for I/O of the one-touch connector
type/connector type compact remote I/O unit into the one-touch connector for
analog I/O accidentally.
Doing so can cause the module to be damaged.
In an unused channel, if terminals remain open, an erratic digital value may be
output.
To prevent this, take any of the following measures.
1. Select Prohibit in the A/D conversion enable/prohibit setting for the unused
channel.
Note that changing the setting from Enable to Prohibit will reduce the
sampling cycle.
2. Short-circuit the input terminals (terminal V+ and V-) of the unused channel.
3. Connect the AG terminal to the GND terminal of the external device.