5 - 26                                                                                                                                                       5 - 26 
MELSEC-A
 
5 PROGRAMMING 
 
(2)  Initial setting by remote device station initialization procedure 
registration function 
(a)  Setting of target station numbers 
Set the station numbers to which initial setting will be made. 
Set the target station numbers to "1" and "4". 
 
 
 
(b)  Selection of procedure registration (part 1) 
Make setting for the AJ65VBTCU-68ADI. 
Click Procedure registration of target station number "1". 
 
(c)  Setting of procedure registration (part 1) 
Set the conditions and execution for the AJ65VBTCU-68ADI. 
 
When the initial data processing request flag (RX18) turns ON and Remote 
device station initialization procedure registration (SB0D) is set, the 
following data are registered to the AJ65VBTCU-68ADI. 
 
Procedure Execution Condition in AJ65VBTCU-68ADI  Execution Data 
A/D conversion enable/prohibit specification: Channel 1, 2: Enable 
(RWw0 :0003
H
) 
CH.1 to CH.4 input range setting : channel 1: 4 to 20mA 
  : channel 2: user range setting 
(RWw1: 20
H
) 
Average processing specification : channel 1: sampling processing 
  : Channel 2: Average processing, number 
of times averaging 
(RWw3: 200
H
) 
CH. 2 average time, number of times setting: Channel 2: 16 times  
(RWw5: 10
H
) 
Initial data processing completion flag (RY18) is turned ON. 
Initial data processing request flag (RX18) turns ON 
Initial data processing request flag (RY19) is turned ON. 
Initial data processing request flag (RX18) turns OFF  Initial data processing completion flag (RY18) is turned OFF. 
Initial data setting completion flag (RX19) turns ON  Initial data setting request flag (RY19) is turned OFF. 
 
(d)  Setting result (part 1) 