16
REQUIREMENT
Disconnect the appliance from the main power supply.
This appliance must be connected to the main power supply by a circuit breaker or switch with a contact
separation of at least 3mm.
Fasten the screws to the terminal with torque of 0.5Nm.
Connections to external equipment
Example of connection to external equipment which is connected to digital input / output connector.
Designation
Input /
Output
item
Central controller side External equipment side
Input / output
conditions
Terminal name Example of circuit
Input / output
conditions
DO1
(Alarm output)
DO2
(Run output)
DO-COM
(Output
common)
Status
output
Allowable
terminal voltage
/ current
DC24V / 35mA
Wiring length:
100 m or less
DI1
(All stop input)
DI2
(All start input)
DI3
(Fire alarm
input)
DI-COM
(Input
common)
Control
input
Non-voltage A
contacts
Pulse or static
* Non voltage
contacts must
be compatible
with minimal
current.
DC5V / 3mA
Pulse width:
300 ms or more
Wiring length:
100 m or less
N
L
35
55
35
55
35 6
Length of stripped power cable Length of stripped TCC-LINK
communication cable
Length of stripped digital Input /
Output communication wire
Attach the supplied clamp filter to the LAN cable.
* Wind the LAN cable around the clamp filter as shown
below when attaching the filter to the cable. After
attaching the filter, fix it to the LAN cable using a
supplied tie-wrap.
* Attach the clamp filter as near the main unit as possible.
LAN cable
Loosen the screw with the screw
driver, insert the digital input / output
communication wire, then tighten
the screw again to fix the wire firmly.
Round pressure
terminal
Attach a round pressure terminal to
the end of each wire of the power
cable, communication cable and
power cable for central controller.
35
Length of stripped RS-485
communication cable
DO1
DO2
DO-COM
Digital
output
5V
5V
5V
DI1
DI2
DI-COM
DI3
Pulse or static
Pulse or static
Static