23
Termination
The termination switches for TCC-LINK are placed in the central controller box. Detach the panel when configuring
termination setting.
NOTE
TCC-LINK connection is terminated on indoor units. Set SW 200 to “Open” for both TCC-LINK 1 and 2.
1
ON
OFF
2 3 4
DS25
<1> Always OFF
• Always set this bit to OFF.
<4> Fire alarm input switching (Set this switch to match the fire alarm input connection set in chapter 4.)
Set OPEN or CLOSE input junction pegged to fire alarm.
• OFF: Set CLOSE input junction pegged to fire alarm.
• ON: Set OPEN input junction pegged to fire alarm.
COM-DI
DI3
COM-DI
DI3
(Fire alarm)(Normal)
COM-DI
DI3
COM-DI
DI3
(Fire alarm)(Normal)
Factory default: All OFF
<2> Synchronization of zone setting data
OFF: With synchronization
ON: Without synchronization
This bit specifies whether to perform synchronous communication of zone setting
data between Smart Manager with data analyzers.
* When this bit is set to ON (without synchronization), synchronous communication
is not performed, and when zone setting is made, the data is not reflected in other
Smart Manager with data analyzers.
<3> Always OFF
• Always set this bit to OFF.
<DS25>
ON
SW200
SW200 TCC-LINK termination switches
TCC-LINK1 Open TCC-LINK1 100Ω
TCC-LINK2 Open TCC-LINK2 Open
TCC-LINK1 Open TCC-LINK1 100Ω
TCC-LINK2 100Ω TCC-LINK2 100Ω
1
ON
2 1
ON
2
1
ON
2 1
ON
2