96
G8000 Series Installation and Operation Manual
TOSHIBA G8000 Series UPS
Installation Planning Guide for 300kVA UPS
Standard System: 480V Input, 480Y/277V Output (P/N T80S3K30KK6XSxx)
Rev. 2.3 Page 3 of 3 G8000-IPG-300kVA
Anchorage pattern:
Install anchor bolts to secure the UPS to the floor.
Use 1/2” (12mm) diameter anchor bolts. TheUPS base has eight pre-drilled 5/8” (16 mm)
holes provided. See the figure below for dimensions and locations.
Anchorage Pattern for G8000 300kVA UPS