G9000 1000kVA OPTIONAL BYPASS FUSE Installation Guide 92932-001 3
Step 6: Loosen bolts to remove the U-shaped conductor connected between bypass terminal and
the contactor 52S.
Dont use the bolts removed from the UPS because it is too long to tighten the optional fuses.
Step 7: Replace the U-shaped conductor with the fuse (Part No.1). Refer to Figure.4 for details.
Step 8: Tighten up bolts along with spring washer and flat washer(Part No.2, 3, 4). And check them.
Figure.3 Example of the installation
Step 09: Secure the UPS access panels.
Step 10: Use the G9000 Series UPS Installation and Operation Manual to restore power to the UPS
in the proper sequence.
Step 11: Restore the UPS to normal operation.
52SU
(Hidden
behind bus)
52SV
52SW
52SU
52SV
52SW
52SU
52SV
52SW
Bolt
+
SW, FW
Removable
U-shaped Conductor
Recommended torque:
57.5 N-m (50 N-m - 65 N-m)
42.4 ft-lbs (36.9 ft-lbs - 47.9 ft-lbs)
(b) After the Installation
(a) Factory Default
Fuse
Label