B-16 1600XPi Series UPS Installation and Operation Manual – 60616-014
Item Brief Description
Description
On LCD
U A D
Svc/
QC
F Default Remark
566 Battery mAh In Battery mAh In - - - R/W R/W 0 Range: 1 – 36000
Units: mAh
567 Time to fully charge battery Batt Charge Time - - - R/W R/W 1440 Range: 1 – 10080
Units: Min
568 Milliamp hour lost in one
month
mAh Lost Slope - - - R/W R/W 38 Range: 0 – 9000
Units: mA/M
569 Total milliamp hour lost Total mAh Lost - - - R/W R/W 0 Range: 0 – 18000
Units: mAh
576 Battery Cabinet 1 Input
Voltage
BC1 Vin R R R R R 0 Units: 0.1 V
578 Battery Cabinet 1 Total Charge
Current
BC1 Chg Current R R R R R 0 Units: 0.1 A
579 Battery Cabinet 1 String 1
Current
BC1 String1 I - - - R R 0 Display this variable based on UPS rating.
580 Battery Cabinet 1 String 2
Current
BC1 String2 I - - - R R 0 Display this variable based on UPS rating.
581 Battery Cabinet 1 String 3
Current
BC1 String3 I - - - R R 0 Display this variable based on UPS rating.
582 Battery Cabinet 1 Status BC1 Status R R R R R 0 Display this variable based on UPS rating.
585 Battery Cabinet 1 Ambient
Temperature
BC1 AmbientTemp R R R R R 0 Units: °C
586 Battery Cabinet 2 Input
Voltage
BC2 Vin R R R R R 0 Units: 0.1 V
588 Battery Cabinet 2 Total Charge
Current
BC2 Chg Current R R R R R 0 Units: 0.1 A
589 Battery Cabinet 2 String 1
Current
BC2 String1 I - - - R R 0 Display this variable based on UPS rating.
590 Battery Cabinet 2 String 2
Current
BC2 String2 I - - - R R 0 Display this variable based on UPS rating.
591 Battery Cabinet 2 String 3
Current
BC2 String3 I - - - R R 0 Display this variable based on UPS rating.
592 Battery Cabinet 2 Status BC2 Status R R R R R 0 Display this variable based on UPS rating.
593 Battery Cabinet 2 Charger
Votlage
BC2 Chg Volt R R R R R 0 Display this variable based on UPS rating.
Units: 0.1 V