B-171600XPi Series UPS Installation and Operation Manual – 60616-014
Item Brief Description
Description
On LCD
U A D
Svc/
QC
F Default Remark
595 Battery Cabinet 2 Ambient
Temperature
BC2 AmbientTemp R R R R R 0 Units: °C
570-2 Battery Cabinet 1 Serial
Number
BC1 Serial No R R R R/W R/W
570-3 Battery Cabinet 1 Firmware
Version
BC1 Fware R R R R R
570-5 Battery Cabinet 1 Hardware
Version
BC1 Hardware - - - R/W R/W
570-6 Battery Cabinet 1 EEPROM
Version
BC1 EEPROM R R R R R
570-7 Battery Cabinet 1 Install Date Ins. Date BC1 R R/W R/W R/W R/W
570-9 Battery Cabinet 2 Serial
Number
BC2 Serial No R R R R/W R/W
570-10 Battery Cabinet 2 Firmware
Version
BC2 Fware R R R R R
570-12 Battery Cabinet 2 Hardware
Version
BC2 Hardware - - - R/W R/W
570-13 Battery Cabinet 2 EEPROM
Version
BC2 EEPROM R R R R R
570-14 Battery Cabinet 2 Install Date Ins. Date BC2 R R/W R/W R/W R/W
571-2 Battery Cabinet
Communication Mode
BC Comm Mode - - - R/W R/W Range: 0 – 4
571-3 Number of External Battery
Cabinet
No Of Ext BC - - - R/W R/W Number of external battery cabinet connected to
UPS (Info Parameter)
Range: 0 – 3
571-4 Input Over Voltage Level BC IP OV Lvl - - R R/W R/W Input Overvpltage fault is disable for software
version 15 and above.
Range: 0 – 5000
571-5 Charger Over Voltage Level BC CH OV Lvl - - R R/W R/W Set charger overvoltage limit. This should be atleast
5% higher than oat votlage.
To Set 343 V, enter 3430.
This parameter aect both battery cabinet.
Range: 0 – 4000
571-7 Ambient Over Temperature
Level
Over Temp Lvl - - R R/W R/W Range: 0 – 100