124-EN123-EN
– 62 –
Type
Pipe-diameter
Draw-out forward Draw-out downward
Gas Liquid
MAP180
MAP200
Ø28.6 Ø15.9
Cut the L-shaped pipe at the horizontal
straight section, then braze the supplied
attachment pipe, and the socket, elbow
and pipe procured locally.
Liquid pipe
Attachment
pipe
Gas pipe
Elbow
Attachment pipe
Balance
pipe
Socket
Pipe
Section
to be cut
Gas
pipe
Pipe
Cut the L-shape pipe at the vertical straight
section, then braze the supplied attachment
pipe, and the socket and pipe procured
locally.
Gas pipe
Attachment
pipe
Balance
pipe
Socket
Pipe
Section
to be cut
Gas
pipe
Liquid pipe
Attachment
pipe
Pipe
Socket
MAP220 Ø28.6 Ø19.1
Extruding margin of copper pipe with are machining: B (Unit: mm)
Copper pipe outer
dia.
When using R410A
tool
When using
conventional tool
9.5
12.7
15.9
19.1
0 to 0.5 1.0 to 1.5
Extruding margin of copper pipe with are tools: A (Unit: mm)
Copper pipe outer
dia.
A
+0
0.4
9.5 13.2
12.7 16.6
15.9 19.7
19.1 24.0
* When using the conventional are tool, to connect R410A pipes with aring, make a margin approx. 0.5mm
longer than that of an R22 pipe so that the are size matches the one specied. It is convenient to use a copper
pipe gauge for size adjustment of the extruding margin.
CAUTION
Coupling size of brazed pipe
Connected section
External size Internal size
K
ØC
G
ØF
Wrap the ball valve in a
wet cloth to keep it cool
and prevent the heat from
the torch from damaging it
when connecting the pipe
to the ball valve on the
gas line.
Cloth
Torch
(Unit: mm)
Standard outer dia.
of connected
copper pipe
Connected section
Min. thickness
of coupling
External size Internal size
Min. depth of
insertion
Oval value
Standard outer dia.
(Allowable difference)
CFKG
6.35 6.35 (±0.03)
6.45
( )
+0.04
0.02
7 6 0.06 or less 0.50
9.52 9.52 (±0.03)
9.62
( )
+0.04
0.02
8 7 0.08 or less 0.60
12.70 12.70 (±0.03)
12.81
( )
+0.04
0.02
9 8 0.10 or less 0.70
15.88 15.88 (±0.03)
16.00
( )
+0.04
0.02
9 8 0.13 or less 0.80
19.05 19.05 (±0.03)
19.19
( )
+0.03
0.03
11 10 0.15 or less 0.80
22.22 22.22 (±0.03)
22.36
( )
+0.03
0.03
11 10 0.16 or less 0.82
28.58 28.58 (±0.04)
28.75
( )
+0.06
0.02
13 12 0.20 or less 1.00
34.92 34.90 (±0.04)
35.11
( )
+0.04
0.04
14 13 0.25 or less 1.20
38.10 38.10 (±0.05)
38.31
( )
+0.08
0.02
15 14 0.27 or less 1.26
41.28 41.28 (±0.05)
41.50
( )
+0.08
0.02
15 14 0.28 or less 1.35
Selection of pipe materials and sizes
¿ Selection of pipe materials
Materials : Phosphorus deoxidation seam-less pipe
Minimum wall thickness for R410A application
Soft Half hard or hard OD (Inch) OD (mm)
Minimum wall thickness
(mm)
OK OK 1/4ʺ 6.35 0.80
OK OK 3/8ʺ 9.52 0.80
OK OK 1/2ʺ 12.70 0.80
OK OK 5/8ʺ 15.88 1.00
No Good OK 3/4ʺ 19.05 1.00
No Good OK 7/8ʺ 22.22 1.00
No Good OK 1-1/8ʺ 28.58 1.00
No Good OK 1-3/8ʺ 34.92 1.20
No Good OK 1-5/8ʺ 41.28 1.40
¿ Capacity code of indoor and outdoor units
For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of
connectable indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2)
NOTE
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable indoor
units differs based on the height difference between the indoor units.
When the height difference between the indoor units is 15m or less: Up to 135% of the capacity code (Equivalent
to HP) of the outdoor unit.
When the height difference between the indoor units is over 15m: Up to 105% of the capacity code.