– 69 –
F-GAS label
This product contains uorinated greenhouse gases
Chemical Name of Gas R410A
Global Warming Potential (GWP) of Gas 2088 (ex.R410A ref.AR4)
CAUTION
1. Stick the enclosed refrigerant label adjacent to the service ports for charging or recovering location and where
possible adjacent to existing nameplates or product information label.
2. Clearly write the charged refrigerant quantity on the refrigerant label using indelible ink. Then, place the
included transparent protective sheet over the label to prevent the writing from rubbing off.
3. Prevent emission of the contained uorinated greenhouse gas. Ensure that the uorinated greenhouse gas is
never vented to the atmosphere during installation, service or disposal. When any leakage of the contained
uorinated greenhouse gas is detected, the leak shall be stopped and repaired as soon as possible.
4. Only qualied service personnel are allowed to access and service this product.
5. Any handling of the uorinated greenhouse gas in this product, such as when moving the product or recharging
the gas, shall comply under (EU) Regulation No. 517/2014 on certain uorinated greenhouse gases and any
relevant local legislation.
6. Periodical inspections for refrigerant leaks may be required depending on European or local legislation.
7. Contact dealers, installers, etc., for any questions.
Heat insulation for pipe
Apply heat insulation of pipe separately at the liquid, gas, and balance sides.
Be sure to use thermal insulator resistant up to 120°C or higher for pipes at the gas side.
Finishing after connecting pipes
After piping connection work has been nished, cover the opening of the piping/wiring panel with the piping
cover, or ll silicon or putty into the space between the pipes.
In case of drawing-out the pipes downward or sideward, also close the openings of the base plate and the side
plate.
Under the opened condition, a problem may be caused due to the entering of water or dust.
When using the piping cover When not using the piping cover
Piping/wiring panel
Drawing-out sideward
Drawing-out
frontward
Drawing-out
downward
Close the opening with the
pipe cover.
Piping/wiring panel
Drawing-out sideward
Fill silicon or putty into the
periphery of the pipes.
Drawing-out
downward
Drawing-out
frontward
¿ Pipe holding bracket
Attach pipe holding brackets following the table below.
Diameter of pipe (mm) Interval
Ø15.9 - Ø19.1 2m
Ø22.2 - Ø41.3 3m
1117101201-3 EN.indd 691117101201-3 EN.indd 69 8/8/2559 BE 3:49 PM8/8/2559 BE 3:49 PM