– 11 –
21-EN 22-EN
Type
Pipe-diameter
Draw-out forward Draw-out downward
Gas Liquid
MAP10A
Ø22.2 Ø12.7
Cut the L-shaped pipe at the horizontal straight
section, then braze the supplied attachment pipe,
and the socket, elbow and pipe procured locally.
Gas pipe
Elbow
Socket
Pipe
Pipe
Liquid pipe
Attachment
pipe
Balance
pipe
Gas
pipe
Section
to be cut
Attachment pipe
Cut the L-shape pipe at the vertical straight
section, then braze the supplied attachment
pipe, and the socket and pipe procured locally.
Gas pipe
Socket
Socket
Pipe
Liquid pipe
Attachment
pipe
Balance pipe
Gas
pipe
Section
to be cut
Attachment
pipe
Pipe
MAP12A
Ø28.6 Ø12.7
MAP14A
MAP16A
MAP180
MAP200
Ø28.6 Ø15.9
Extruding margin of copper pipe with fl are machining: B (Unit: mm)
Copper pipe outer
dia.
When using R410A
tool
When using
conventional tool
9.5
12.7
15.9
19.1
0 to 0.5 1.0 to 1.5
Extruding margin of copper pipe with fl are tools: A (Unit: mm)
Copper pipe outer
dia.
A
+0
-0.4
9.5 13.2
12.7 16.6
15.9 19.7
19.1 24.0
* When using the conventional flare tool, to connect R410A pipes with flaring, make a margin approx. 0.5mm
longer than that of an R22 pipe so that the flare size matches the one specified. It is convenient to use a copper
pipe gauge for size adjustment of the extruding margin.
CAUTION
Wrap the ball valve in a wet cloth to keep it cool and prevent the heat from the
torch from damaging it when connecting the pipe to the ball valve on the gas line.
Coupling size of brazed pipe
Connected section
External size Internal size
K
ØC
G
ØF
(Unit: mm)
Standard outer dia.
of connected
copper pipe
Connected section
Min. thickness
of coupling
External size Internal size
Min. depth of
insertion
Oval value
Standard outer dia.
(Allowable difference)
CFKG
6.35 6.35 (±0.03)
6.45 (
+0.04
−0.02
)
7 6 0.06 or less 0.50
9.52 9.52 (±0.03)
9.62 (
+0.04
−0.02
)
8 7 0.08 or less 0.60
12.70 12.70 (±0.03)
12.81 (
+0.04
−0.02
)
9 8 0.10 or less 0.70
15.88 15.88 (±0.03)
16.00 (
+0.04
−0.02
)
9 8 0.13 or less 0.80
19.05 19.05 (±0.03)
19.19 (
+0.03
−0.03
)
11 10 0.15 or less 0.80
22.22 22.22 (±0.03)
22.36 (
+0.03
−0.03
)
11 10 0.16 or less 0.82
28.58 28.58 (±0.04)
28.75 (
+0.06
−0.02
)
13 12 0.20 or less 1.00
34.92 34.90 (±0.04)
35.11 (
+0.04
−0.04
)
14 13 0.25 or less 1.20
38.10 38.10 (±0.05)
38.31 (
+0.08
−0.02
)
15 14 0.27 or less 1.26
41.28 41.28 (±0.05)
41.50 (
+0.08
−0.02
)
15 14 0.28 or less 1.35
■ Selection of pipe materials and sizes
◆ Selection of pipe materials
Materials : Phosphorus deoxidation seam-less pipe
Minimum wall thickness for R410A application
Soft
Half hard or hard OD (Inch) OD (mm) Minimum wall thickness (mm)
OK OK 1/4” 6.35 0.80
OK OK 3/8” 9.52 0.80
OK OK 1/2” 12.70 0.80
OK OK 5/8” 15.88 1.00
No Good OK 3/4” 19.05 1.00
No Good OK 7/8” 22.22 1.00
No Good OK 1-1/8” 28.58 1.00
No Good OK 1-3/8” 34.92 1.20
No Good OK 1-5/8” 41.28 1.40
◆ Capacity code of indoor and outdoor units
• For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
• The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of
connectable indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2)
NOTE
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable indoor
units differs based on the height difference between the indoor units.
• When the height difference between the indoor units is 15m or less: Up to 135% of the capacity code (Equivalent
to HP) of the outdoor unit.
• When the height difference between the indoor units is over 15m: Up to 105% of the capacity code.