37-EN 38-EN
Power wiring selection
Select the power supply cabling of each outdoor unit from the following speci cations:
Cable 5-core, in conformance with design H07 RN-F or 60245 IEC 66.
To decide nominal cross sectional area of conductor, refer to following table of Maximum Overcurrent Protection
(Amps).
Standard model
MCA: Minimum Circuit Amps
MOCP: Maximum Overcurrent Protection (Amps)
Model name
Power Supply
MCA
(A)
MOCP
(A)
Phase and frequency Nominal Voltage
MMY-MAP0806*
3N~50Hz 380-400-415V
20.5 25
MMY-MAP1006* 21.5 25
MMY-MAP1206* 26.1 32
MMY-MAP1406* 31.0 40
MMY-MAP1606* 35.8 40
MMY-MAP1806* 40.6 50
MMY-MAP2006* 44.9 50
MMY-AP2216*
3N~50Hz 380-400-415V
47.6 63
MMY-AP2416* 52.2 63
MMY-AP2616* 57.1 63
MMY-AP2816* 62.0 80
MMY-AP3016* 66.8 80
MMY-AP3216* 71.6 80
MMY-AP3416* 76.4 100
MMY-AP3616* 81.2 100
MMY-AP3816* 85.5 100
MMY-AP4016* 89.8 100
MMY-AP4216*
3N~50Hz 380-400-415V
93.0 125
MMY-AP4416* 97.8 125
MMY-AP4616* 102.6 125
MMY-AP4816* 107.4 125
MMY-AP5016* 112.2 125
MMY-AP5216* 117.0 160
MMY-AP5416* 120.8 160
MMY-AP5616* 125.6 160
High-ef ciency model
MCA: Minimum Circuit Amps
MOCP: Maximum Overcurrent Protection (Amps)
Model name
Power Supply
MCA
(A)
MOCP
(A)
Phase and frequency Nominal Voltage
MMY-MAP10A6HT8P-ME
3N~50Hz 380-400-415V
21.5 25
MMY-MAP12A6HT8P-ME 26.1 32
MMY-MAP14A6HT8P-ME 31.0 40
MMY-MAP16A6HT8P-ME 35.8 40
MMY-AP1826HT8P-ME
3N~50Hz 380-400-415V
42.0 50
MMY-AP2026HT8P-ME 43.0 63
MMY-AP2226HT8P-ME 47.6 63
MMY-AP2426HT8P-ME 52.2 63
MMY-AP2626HT8P-ME 57.1 63
MMY-AP2826HT8P-ME 62.0 80
MMY-AP3026HT8P-ME 66.8 80
MMY-AP3226HT8P-ME 71.6 80
MMY-AP3426HT8P-ME
3N~50Hz 380-400-415V
73.7 100
MMY-AP3626HT8P-ME 78.3 100
MMY-AP3826HT8P-ME 83.2 100
MMY-AP4026HT8P-ME 88.1 100
MMY-AP4226HT8P-ME 92.9 125
MMY-AP4426HT8P-ME 97.7 125
L1L
2
L3 N
L1L2L3 N L1L2L
3
N
Circuit breaker
(Earth leakage breaker)
Main switch
(Fuse)
1117101401-3_EN.indd 191117101401-3_EN.indd 19 1/12/16 3:46 PM1/12/16 3:46 PM