– 25 –
49-EN 50-EN
Switch setting (setting example when controlling 2 or more refrigerant lines centrally)
Outdoor units (setting manually)
*The items in bold font must be set manually.
Outdoor unit’s
interface
P.C. board
Header unit
Follower
unit
Header unit
Follower
unit
Header unit Factory default
SW13, 14
(Line (system) address)
1
(No setting
required)
2
(No setting
required)
3 1
DIP switch 2 of SW30
(Terminator of indoor/
outdoor communication
line and central control
line)
ON
(No setting
required)
Set to OFF
after setting
addresses.
(No setting
required)
Set to OFF
after setting
addresses.
ON
Relay connector
Connect after
setting
addresses.
Open
Connect after
setting
addresses.
Open
Connect after
setting
addresses.
Open
A
U1 U2
U3 U4 U3 U4
U5 U6 U1 U2 U5 U6 U1 U2U1 U2 U5 U6 U1 U2 U5 U6 U5 U6
U1 U2 U1 U2 U1 U2 U1 U2 U1 U2
BAB AB
U3 U4 U3 U4 U3 U4
AB AB
Header unit Follower unit Follower unitHeader unit Header unit
Central
control
controller
Relay
connector
Remote
controller
Individual
Indoor units
(automatic setting)
Group
Remote
controller
Remote
controller
Remote
controller
Relay
connector
Relay
connector
Line (system) address 1 1 2 2 3
Indoor unit address 1 2 1 2 1
Group address 0 0 1 2 0
CAUTION
Relay connector connection
Never connect relay connectors between the [U1, U2] and [U3, U4] terminals before completing address setting of
all the refrigerant lines. Otherwise, the addresses cannot be set correctly.
Manual address setting using the remote controller
Procedure when setting indoor units’ addresses first under the condition that indoor wiring has been completed
and outdoor wiring has not been started (manual setting using the remote controller)
Wiring example of 2 refrigerant lines
Refrigerant line 1
Outdoor
unit
Remote
controller
Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 1 Indoor unit 2
Outdoor
unit
Refrigerant line 2
Line (system) address 1 1 1 2 2
Indoor unit address 1 2 3 1 2
Group address
1
Header unit
2
Follower unit
2
Follower unit
2
Follower unit
2
Follower unit
In the example above, disconnect the remote controller connections between the indoor units and
connect a wired remote controller to the target unit directly before address setting.
ON / OFF
TEMP.
TIME
SET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
11
4, 7, 10
2, 5, 8
3, 6, 9
1
SET DATA
CODE No.
Pair the indoor unit to set and the remote controller one-to-one.
Turn on the power.
1 Push and hold the
SET
,
CL
, and
TEST
buttons at the same time for more than 4 seconds.
LCD starts ashing.
1117101401-3_EN.indd 251117101401-3_EN.indd 25 1/12/16 3:18 PM1/12/16 3:18 PM