96 Q9 ASD Installation and Operation Manual
BIN Reference 2
Program Frequency Settings
This parameter is used to set the speed of the BIN input terminals when the BIN
terminals are used as the control input.
This parameter sets the BIN input signal that is associated with BIN Frequency 2.
This value is entered as 0% to +100% of the BIN input signal range.
See BIN Reference 1 (F228) for further information on this setting.
Direct Access Number — F230
Parameter Type — Numerical
Factory Default100
Changeable During Run — Yes
Minimum — 0
Maximum100
Units — %
BIN Frequency 2
Program Frequency Settings
This parameter is used to set the speed of the BIN input terminals when the BIN
terminal are used as the control input.
This parameter sets BIN Frequency 2 and is the frequency that is associated with
the setting of BIN Reference 2.
See BIN Reference 1 (F228) for further information on this setting.
Direct Access Number — F231
Parameter Type — Numerical
Factory Default60.00
Changeable During Run — Yes
Maximum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
PG Reference 1
Program Frequency Settings
This parameter is used to set the gain and bias of the PG input terminal of the
option board when a shaft-mounted encoder is used as the control input while
operating in the Speed Control mode.
Note: See the PG Option Board Instruction Manual P/N 58687 for more
information.
PG Input Speed Control Setup
Perform the following setup to allow the system to receive Speed control input at
the PG input terminal:
Program Utility Group Command Mode Option Board.
Program Utility Group Frequency Mode 1 Pulse (Option).
Provide a Run command (F and/or R).
Speed Control
Perform the following setup to allow the system to perform Speed control from
the PG input terminals:
•Set PG Frequency 1 (F235).
•Set the PG input value (F234) that represents PG Frequency 1.
•Set PG Frequency 2 (F237).
•Set the PG input value (F236) that represents PG Frequency 2.
Once set, as the PG input pulse count rate changes, the output frequency of the
ASD will vary in accordance with the above settings.
This parameter sets the PG input pulse count that represents PG Frequency 1. The
range of values for this parameter is 0% to 100% of the PG input pulse count
range.
Note: Further application-specific PG settings may be performed from
the following path: Program Feedback Setting
PG Settings.
Direct Access Number — F234
Parameter Type — Numerical
Factory Default0.0
Changeable During Run — Yes
Minimum — 0
Maximum — 100.0
Units — %
Frequency Settings
F230 F234