102 Q9 ASD Installation and Operation Manual
Jog Stop Control
Program Frequency Settings
This parameter sets the stopping method used while operating in the Jog mode.
Note: This parameter setting is used for the Jog operation only. The
Emergency Off stopping method setting of parameter F603 has
priority over this setting and changes made here do not affect the
function or setting of parameter F603.
Settings:
0 — Deceleration
1 — Coast
2 — DC Injection Braking
Direct Access Number — F261
Parameter Type — Selection List
Factory Default — Deceleration
Changeable During Run — Yes
Panel Operation Jog Mode
No Path — Direct Access Only
This parameter Enables/Disables the Jog command. When disabled the Jog
command is ignored.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F262
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
F261 F262