110 Q9 ASD Installation and Operation Manual
Number of Retries
Program Protection
After a trip has occurred, this parameter sets the number of times that an
automatic system restart is attempted for a qualified trip.
The trip conditions listed below will not initiate the automatic Retry/Restart
function:
Input Phase Loss (Input Phase Failure)
Output Phase Loss (Output Phase Failure)
Output Current Protection Fault
Output Current Detector error
Load Side Over-Current At Start
Earth Fault (Ground Fault)
Over-Current During Acceleration
Arm Over-Current at start-up
Low-Current
Voltage Drop In Main Circuit
EEPROM Data Fault (EEPROM Fault)
Flash Memory/Gate Array/RAM-ROM Fault
CPU Fault
Emergency Off (EMG)
Communication Error
Option Fault
Sink/Source Setting Error
Overspeed Error
Over-Torque
•Key Error
External Thermal Error
Externally-Controlled Interrupt
See the section titled System Setup Requirements on pg. 8 for more information
on this setting.
Direct Access Number — F303
Parameter Type — Numerical
Factory Default00
Changeable During Run — Yes
Minimum — 00
Maximum — 10
F303 F303