Q9 ASD Installation and Operation Manual 125
V/I Input Gain
No Path — Direct Access Only
This parameter is used to fine tune the gain of the V/I input terminals.
Note: See note on pg. 40 for more information on the V/I terminal.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and adjusting this
setting to provide an output of 100% from the ASD.
Direct Access Number — F471
Parameter Type — Numerical
Factory Default124
Changeable During Run — Yes
Minimum — 0
Maximum255
RR Input Bias
No Path — Direct Access Only
This parameter is used to fine tune the bias of the RR input terminal when this
terminal is used as the control input while operating in the Speed Control mode
or the Torque Control mode.
This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.
This is accomplished by setting the input source to zero and adjusting this setting
to provide an output of zero from the ASD.
Direct Access Number — F472
Parameter Type — Numerical
Factory Default128
Changeable During Run — Yes
Minimum — 0
Maximum255
RR Input Gain
No Path — Direct Access Only
This parameter is used to fine tune the gain of the RR input terminal when this
terminal is used as the control input while operating in the Speed Control mode
or the Torque Control mode.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and adjusting this
setting to provide an output of 100% from the ASD.
Direct Access Number — F473
Parameter Type — Numerical
Factory Default154
Changeable During Run — Yes
Minimum — 0
Maximum255
RX Input Bias
No Path — Direct Access Only
This parameter is used to fine tune the bias of the RX input terminal when this
terminal is used as the control input while operating in the Speed Control mode
or the Torque Control mode.
This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.
This is accomplished by setting the input source to zero and adjusting this setting
to provide an output of zero from the ASD.
Direct Access Number — F474
Parameter Type — Numerical
Factory Default127
Changeable During Run — Yes
Minimum — 0
Maximum255
F471 F474