Q9 ASD Installation and Operation Manual 143
MON2 Terminal Meter Adjustment
No Path — Direct Access Only
This parameter is used to set the gain of the MON2 output terminal and is used in
conjunction with the settings of parameter F674.
See parameter F674 for more information on this setting.
Direct Access Number — F675
Parameter Type — Numerical
Factory Default — 682
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
FP Terminal Assignment
Program Output Terminals
This parameter sets the functionality of the FP output terminal to any of the user-
selectable functions listed in Table 6 on pg. 189.
As the assigned function changes in magnitude or frequency, the pulse count of
the FP output terminal pulse train changes in direct proportion to changes in the
assigned function.
Note: The duty cycle of the output pulse train remains at 65 ±5.0 µS.
This parameter is used in conjunction with parameter F677.
Direct Access Number — F676
Parameter Type — Selection List
Factory Default — Output Frequency
Changeable During Run — Yes
FP Terminal Scaling
Program Output Terminals
This parameter scales the FP output terminal by setting the pulses-per-second
output signal for a given assigned input value.
See F676 for more information on this parameter.
Direct Access Number — F677
Parameter Type — Numerical
Factory Default — 3.84
Changeable During Run — Yes
Minimum — 1.00
Maximum — 43.20
Units — Pulses/Second
FP Terminal Scaling
No Path — Direct Access Only
This parameter is used to select the degree of filtering to be applied to the DC bus
voltage and the output DC voltage.
Direct Access Number — F678
Parameter Type — Numerical
Factory Default — 64
Changeable During Run — Yes
Minimum — 4
Maximum — 100
Units — ms
FM Voltage/Current Output Switching
Program AM/FM
This parameter is used to select the type of output signal provided at the FM
terminal
(i.e., Voltage or Current).
The output voltage and current range is 0 – 10 VDC and 0 – 20 mA, respectively.
See F005 for more information on this setting.
Settings:
0 — 0 – 10 V
1 — 0 – 20 mA
Direct Access Number — F681
Parameter Type — Selection List
Factory Default — 0 – 20 mA
Changeable During Run — No
F675 F681