Q9 ASD Installation and Operation Manual 35
Command Control Selections
The following is a listing with descriptions of the
Command Mode (F003) selections (Program
Utility Group Command Mode).
Settings:
0 — Terminal Block
Allows for Command control input via the
Terminal Board.
1 — Panel Keypad
The Panel Keypad is unavailable at the time of this release.
2 — RS485 (2-Wire)
Used for EOI command control.
3 — RS485 (4-Wire)
Use this setting if using a remotely-mounted EOI for command control. Connect the EOI to the
RJ45 connector of the Terminal Board.
4 — (Communication) Option Board
Use this setting if using the optional Communication Board for command control.
Frequency Control
Selections
The following is a listing with descriptions of the
Frequency Mode (F004) selections (Program
Utility Group Frequency Mode 1).
Settings:
1 — V/I (VI/II)
Used when a 0 to 10 VDC analog input or a 4 – 20 mA (or 0 to 1 mA) DC current input is used
as the speed control input. Only one input signal type may be used at a time. Set SW301 to the
desired signal type.
2 — RR
Used for a 0 to 10 VDC analog input signal.
3 — RX
Used for a -10 to +10 VDC analog input signal.
4 — Panel Keypad
The Panel Keypad is unavailable at the time of this release.
5 — RS485 (2-Wire)
Used for EOI frequency control.
6 — RS485 (4-Wire)
Use this setting if using a remotely-mounted EOI for frequency control. Connect the EOI to the
RJ45 connector of the Terminal Board.