84 Q9 ASD Installation and Operation Manual
V/I Reference 2
Program Frequency Settings
This parameter is used to set the gain and bias of the isolated V/I input terminal
when the V/I terminal is used as the control input while operating in the Speed
Control mode or the Torque Control mode.
This parameter sets the V/I input level that is associated with V/I Frequency 2
when operating in the Speed control mode or is associated with the V/I Torque
Reference 2 when operating in the Torque Control mode.
This value is entered as 0% to 100% of the V/I input signal range.
See V/I Reference 1 for more information on this setting when used for Speed
control.
See V/I Torque Reference 1 (F205) for more information on this setting when
used for Torque Control.
Direct Access Number — F203
Parameter Type — Numerical
Factory Default100
Changeable During Run — Yes
Minimum — 0
Maximum100
Units — %
V/I Frequency 2
Program Frequency Settings
This parameter is used to set the gain and bias of the isolated V/I input terminal
when the V/I terminal is used as the control input while operating in the Speed
Control mode.
This parameter sets V/I Frequency 2 and is the frequency that is associated with
the setting of V/I Reference 2 when operating in the Speed Control mode.
See V/I Reference 1 (F201) for more information on this setting.
Direct Access Number — F204
Parameter Type — Numerical
Factory Default60.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
F203 F204